Address High
Address Low
Name
Description
Units
Scale
84
0x054
85
0x055 Default Output Periodic
Boost Period
Interval between periodic boost
events (0 = disabled)
Sec
1
86
0x056
87
0x057 Default Output AC Line
Frequency
AC Line Frequency
Hz
10
88
0x058
89
0x059 Default Output AC Line
Voltage 1
AC Line 1 Voltage
V
32768
90
0x05A
91
0x05B Default Output AC Line
Current 1
AC Line 1 Current
A
32768
92
0x05C
93
0x05D Default Output AC Line
Voltage 2
AC Line 2 Voltage (Not applicable to
single phase chargers)
V
32768
94
0x05E
95
0x05F Default Output AC Line
Current 2
AC Line 2 Current (Not applicable to
single phase chargers)
A
32768
96
0x060
97
0x061 Default Output AC Line
Voltage 3
AC Line 3 Voltage (Not applicable to
single phase chargers)
V
32768
98
0x062
99
0x063 Default Output AC Line
Current 3
AC Line 3 Current (Not applicable to
single phase chargers)
A
32768
100
0x064
101
0x065 Default Output Battery
Check Duration
Duration of battery check
Sec
1
102
0x066
103
0x067 Default Output Battery
Check Interval
Interval between scheduled
automatic battery checks
Sec
1
104
0x068
105
0x069 Default Output Number of
Chargers
Number of chargers detected on
SENSbus, 0 - 30
Num
1
106
0x06A
107
0x06B Default Output Redundancy
Level
Number of redundant output
chargers
Num
1
108
0x06C
109
0x06D Default Output Extended
Status
Current state of alarm/comms circuit
board (see Extended Status Bit
Definition)
bit
1
128
0x080
129
0x081 Default Output Maximum
Power
Maximum rated power
V/Cell
32768
130
0x082
131
0x083 Default Output Maximum
Voltage
Maximum rated voltage in x.xx V
V/Cell
32768
132
0x084
133
0x085 Default Output Maximum
Current
Maximum rated current in x.xx A
A
32768
134
0x086
135
0x087 Default Output Program
Float Setting
Float Cell Voltage used in Program
Mode
V/Cell
32768
136
0x088
137
0x089 Default Output Program
Boost Setting
Boost Cell Voltage used in Program
Mode
V/Cell
32768
138
0x08A
139
0x08B Default Output Program
Mode
Mode callouts for Program Mode
setting (battery type… etc.)
Custom
1
140
0x08C
141
0x08D Default Output Program
Cell Count
Number of cells set in Program Mode
Cells
32768
142
0x08E
143
0x08F Default Output Program
Temp comp slope
In 0.xx°C per output volt x -1
°C/V
32768
144
0x090
145
0x091 Default Output Low DC
Program
Alarm setpoint for low DC (used for
Program Mode setting)
V/Cell
32768
146
0x092
147
0x093 Default Output Low Crank
Program
Alarm setpoint for low Crank (used
for Program Mode setting)
V/Cell
32768
148
0x094
149
0x095 Default Output Low Current
Program
Alarm setpoint for low Current(used
for Program Mode setting)
A
32768
152
0x098
153
0x099 Default Output High DC
Program
Alarm setpoint for high DC (used for
Program Mode setting)
V/Cell
32768
154
0x09A
155
0x09B Default Output OVSD
Program
Alarm setpoint for OVSD (used for
Program Mode setting)
V/Cell
32768
156
0x09C
157
0x09D Default Output Batt
Alarm setpoint for Batt Discharge
V/Cell
32768