background image

SENS MicroGenius S2/S4 Technical Manual 

 

 

 

  44 

 

 

Use the DeviceInstaller software to change the IP Address of the TCP/IP module by using the 

Assign IP command in the menu toolbar. The software will request the Device Identification 

(hardware address) of the module. This address is identified as “MAC” and is displayed on the 

charger label located on the outside of the charger enclosure. This address is unique to each 

charger. Follow the software dialogue to complete the IP address setup. 

11.2.

 

Modbus Holding Registers 

Address High 

Address Low 

Name 

Description 

Units 

Scale 

Factor 

Decimal

 

Hex

 

Decimal

 

Hex

 

0x000 

0x001  System Serial Number 

Serial Number of System the device 

was built into and shipped part of 

Num 

0x002 

0x003  Program Revision 

Version of the main program 

Num 

0x004 

0x005  Bootloader Version 

Version of bootloader 

Num 

0x006 

0x007  Type 

Device type 

Enum 

0x008 

0x009  Serial 

Serial Number of the Device 

Num 

10 

0x00A 

11 

0x00B  Build Date 

Year (16bit), month(8bit),day(8bit) 

Num 

12 

0x00C 

13 

0x00D  Model Num 1_4 

Model number character 

bit 

14 

0x00E 

15 

0x00F  Model Num 5_8 

Model number character 

bit 

16 

0x010 

17 

0x011  Model Num 9_12 

Model number character 

bit 

18 

0x012 

19 

0x013  Model Num 13_16 

Model number character 

bit 

20 

0x014 

21 

0x015  Model Num 17_20 

Model number character 

bit 

22 

0x016 

23 

0x017  Model Num 21_24 

Model number character 

bit 

24 

0x018 

25 

0x019  Model Num 25_28 

Model number character 

bit 

26 

0x01A 

27 

0x01B  Model Num 29_32 

Model number character 

bit 

28 

0x01C 

29 

0x01D  Watt Minutes High 

For Odometer 

bit 

30 

0x01E 

31 

0x01F  Watt Minutes Low 

For Odometer 

bit 

32 

0x020 

33 

0x021  Minutes in Charge High 

For Odometer 

bit 

34 

0x022 

35 

0x023  Minutes in Charge Low 

For Odometer 

bit 

36 

0x024 

37 

0x025  Number of Cranks Detected  Number of times the crank logger has 

been tripped 

Num 

38 

0x026 

39 

0x027  Number of Cranks Under 

Threshold 

Number of times the crank logger has 

detected a bad battery 

Num 

40 

0x028 

41 

0x029  Autoboost Lockout 

Duration 

Autoboost Lockout Duration 

Num 

60 

64 

0x040 

65 

0x041  Default Output Status 

Current State of the charger (see 

Status Definition below) 

Bits 

66 

0x042 

67 

0x043  Default Output Alarms 

Alarm status bits (see Alarm Bit 

Definition below) 

Bits 

68 

0x044 

69 

0x045  Default Output Batt Voltage  Voltage currently being supplied by 

the charger to the battery 

32768 

70 

0x046 

71 

0x047  Default Output Current 

Current currently being supplied by 

the charger to the battery 

32768 

72 

0x048 

73 

0x049  Default Output Power  

Power currently being supplied by 

the charger 

32768 

74 

0x04A 

75 

0x04B  Default Output Factory 

Float Setting 

Float Cell Voltage set at Factory 

V/cell 

32768 

76 

0x04C 

77 

0x04D  Default Output Factory 

Boost Setting 

Boost Cell Voltage set at Factory 

V/cell 

32768 

78 

0x04E 

79 

0x04F  Default Output Remote 

Temp  

Remote temp sense temperature in 

0.0°C 

°C 

32768 

80 

0x050 

81 

0x051  Default Output Internal 

Temp 

Ambient air temperature near 

charger input connectors (tp 1) 

°C 

32768 

82 

0x052 

83 

0x053  Default Output Boost 

Elapsed Time 

Boost time  

Sec 

Содержание MicroGenius S2

Страница 1: ...rough Friday or visit our website Copyright Stored Energy Systems LLC 2018 The SENS name logo MicroGenius HELIX and Dynamic Boost are trademarks of Stored Energy Systems LLC SENS Part Number 101330 Do...

Страница 2: ...Apply AC Input Voltage 24 7 4 Power Off 24 8 ALARMS LEDS AND DISPLAY 24 8 1 LED Indicators 24 8 2 Individual Alarm Relay Contacts 25 8 3 LCD Panel 26 8 4 Alarm Definitions 26 9 OPERATION 32 9 1 Chargi...

Страница 3: ...STRUCTIONS EACH TIME YOU USE THE CHARGER 1 8 2 To reduce the risk of battery explosion follow these instructions and those published by the battery manufacturer and the manufacturer of any equipment y...

Страница 4: ...1 Be sure area around battery is well ventilated while battery is being charged 1 10 2 Ensure battery terminals are clean and properly tightened Be careful to keep corrosion from coming in contact wit...

Страница 5: ...odbus TCP IP native SENSbus USB 2 J1939 and Modbus RS 485 with RJ 45 to terminal block adapter 3 J1939 Modbus TCP IP USB RJ45 to terminal block adapter E Configuration 0 Standard R 19in rack mount ear...

Страница 6: ...ssion CEC Title 20 Appliance Efficiency Regulations Power factor 95 typical at maximum rated load current and boost charge voltage DC output Voltage 12 24V nominal multiple output assignments optional...

Страница 7: ...m is not sinusoidal or is distorted the AC voltage will not be reported accurately Status messages 20 character display of status and alarm messages Alarms Alarms Factory set and field reconfigurable...

Страница 8: ...ns 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Seismic rigid and non structure wa...

Страница 9: ...ptional Dimensions See drawings and dimensions at back of manual Weight S2 case size 13 lbs 5 9 kg maximum S4 case size 32 lbs 14 5 kg maximum Connections AC and DC terminal blocks or breakers optiona...

Страница 10: ...ten to 2 0 In Lb 0 22 Nm SENSbus CONNECT CHARGER LOAD SHARING CABLE REMOTE ACCESSORIES OR SENS SETUP UTILITY TO RJ 45 CONNECTOR CONNECT GROUND WIRE 28 16 AWG 0 08 1 5 mm2 Tighten to 50 In Lb 5 6 Nm CO...

Страница 11: ...45 CONNECT AC WIRES AT BREAKER TERMINALS 14 2 AWG 2 5 35 mm2 Tighten to 43 In Lb 4 9 Nm CONNECT REMOTE TEMPERATURE SENSOR 28 16 AWG 0 08 1 5 mm2 Tighten to 2 0 In Lb 0 22 Nm SENSbus CONNECT CHARGER L...

Страница 12: ...5 35 mm2 Tighten to 3 2 50 In Lb 5 6 Nm 6 4 45 In Lb 5 1 Nm 8 40 In Lb 4 5 Nm 14 10 35 In Lb 4 0 Nm CONNECT REMOTE TEMPERATURE SENSORS One sensor per output 28 16 AWG 0 08 1 5 mm2 Tighten to 2 0 In Lb...

Страница 13: ...charger at least 6 inches 15 cm at the top at least 4 inches 10 16 cm at the bottom at least 0 5 inches 1 27 cm on each side Operating temperature ranges stated above assume stated clearances 5 1 5 M...

Страница 14: ...ld be rated for use at 75 C or higher 6 1 2 Coordinate the AC input conductor size with the customer provided branch circuit protection device 6 1 3 For best performance and recharge time refer to the...

Страница 15: ...al on charger 6 2 2 Connect the equipment grounding conductor to the ground lug in the charger see Figures 1 3 This lug is marked with the ground symbol This should always be the first wire connected...

Страница 16: ...2 AWG 0 5 35 mm2 4 22 In Lb 2 5 Nm 4 40 In Lb 4 5 Nm Phillips P2 S4 Breaker 50A 14 2 AWG 2 5 35 mm2 50A 12 AWG 2 0 4 70 mm2 45 In Lb 5 1 Nm 5 16 inch flat head S4 Terminal Block 14 AWG 2 0 2 5 70 mm2...

Страница 17: ...d Breaker Rating Charger Rated Output Current Amps AC Input Current Amps Optional AC Breaker Rating Amps 15 4 15 20 8 15 25 8 15 30 8 15 35 12 15 45 12 15 50 16 20 60 16 20 6 5 Alarm Connections See c...

Страница 18: ...TB1 1 COM TB1 4 COM TB2 1 COM TB2 4 COM TB2 7 Open on alarm normally closed OK TB1 2 OK TB1 5 OK TB2 2 OK TB2 5 Defaults to OK with no AC and DC power OK TB2 8 Close on alarm normally open FAIL TB1 3...

Страница 19: ...1 6 Defaults to FAIL with no AC input FAIL TB2 3 Defaults to FAIL with no AC and DC power FAIL TB2 6 FAIL TB2 9 Defaults to FAIL with no AC and DC power Summary alarm includes AC Fail Charger Fail Bat...

Страница 20: ...n the inside front cover see Figures 1 3 for location in charger and Figure 7 for detail Two RJ 45 ports are provided The ports are in parallel and either port may be used See Table 10 for connector p...

Страница 21: ...cuit board located on the inside front cover see Figures 1 3 for location in charger and Figure 7 for detail Two RJ 45 ports are provided The ports are in parallel and either port may be used See Tabl...

Страница 22: ...e SENSbus RJ 45 ports on each charger to automatically initiate load sharing Two SENSbus RJ 45 ports are provided on the inside panel between the AC and DC connections see Figures 11 12 The ports are...

Страница 23: ...the communications bus The remote accessory may be connected to multiple chargers In this case the remote accessory chargers or other equipment may be located at the ends of the communications bus En...

Страница 24: ...tting is appropriate when charging ultracapacitors rather than batteries see section 9 5 U12 indicates a 12V ultracapacitor and U24 indicates a 24V ultracapacitor WARNING ULTRACAPACITORS ACCEPT AND DI...

Страница 25: ...d share fail SOLID GREEN DOUBLE FLASH RED AC good load sharing DC negative connection open or load sharing charger address fault SOLID RED SOLID GREEN AC fail DC voltage good SOLID RED SOLID YELLOW AC...

Страница 26: ...ltiple outputs The front panel LCD will indicate the alarm and which output is affected 8 4 1 AC Line Failure Indicates AC input voltage is not applied or is outside of allowed 90 265 VAC range Activa...

Страница 27: ...50 25 00 Ultracapacitor 14 40 24 00 MAR VRLA 12 00 24 00 AGM 12 00 24 00 NCD 12 00 24 00 NGN VRLA 12 00 24 00 AGM 12 00 24 00 NCD 12 00 24 00 PSP N A 10 20 20 40 Configuration Code displayed on charge...

Страница 28: ...on charger label 8 4 6 Charger Failure Indicates the charger is not able to provide the current demanded by the battery and or load or is providing more current than the charger s control system is c...

Страница 29: ...o Fail state after delay when alarm is assigned to relay contacts 8 4 10 Incompatible Battery Indicates a 12V battery is connected to a 24V charger The charger operates for approximately 5 minutes whi...

Страница 30: ...ut either the maximum current setting or maximum power output whichever occurs first Alarm communications circuit board CURRENT LIMIT relay contacts change to Fail state after delay when alarm is assi...

Страница 31: ...alarm setpoint Chargers intended for genset applications are shipped with the low current alarm disabled Chargers intended for marine and standby power applications are shipped with the low current al...

Страница 32: ...to the charger are in an alarm state Activates flashing green red DC LED Alarm communications circuit board INDIVIDUAL CHARGER relay contacts change to Fail state after delay when alarm is assigned t...

Страница 33: ...risks of both overcharging and undercharging associated with manual or automatic boost timers or earlier generation automatic boost control systems Dynamic Boost is automatically used by the charger d...

Страница 34: ...ion is required by the operator HELIX mode can be enabled disabled using the keypad the SENS Setup Utility or by selecting a different battery type HELIX mode adds two DC output voltage settings to th...

Страница 35: ...for chargers with multiple outputs Each output is configured independently Upon completion of the test the LCD will display whether the test passed or failed for ten seconds or until the Enter key is...

Страница 36: ...ep 3 or to adjust values Step 4 to return to main fields Step 5 to return to Home screen 9 10 3 Menu Options Input output temperature and alarm status are displayed on the front panel LCD by default P...

Страница 37: ...tage Adjust output Float voltage from 8 to 34V must be greater than 60 of Boost setting Boost Voltage Adjust output Boost voltage from 8 to 34V must be same or greater than Float setting must not be g...

Страница 38: ...LA power supply or ultracapacitor Battery Select cells Adjust number of series cells in battery string Batt Commission voltage Adjust battery commissioning output voltage from float voltage to 34V mus...

Страница 39: ...iew internal rail voltages for troubleshooting purposes Correct values are approximately 3 3V 5V and 11V UI Access Control Select allowed user interface access Access options include read only viewing...

Страница 40: ...o SENSbus RJ 45 ports are provided on the inside panel between the AC and DC connections see Figures 1 3 for location in charger The ports are in parallel and either port may be used for the SENSbus A...

Страница 41: ...A Load sharing will not occur if non corresponding outputs are connected e g do not connect output A to output B The LOAD SHARE FAIL alarm will occur any time a charger is unable to load share If a c...

Страница 42: ...ically begin using J1939 communications after connecting the charger to the network Use the SENS Setup Utility to adjust J1939 settings e g baud rate vehicle system instance etc if required 10 1 J1939...

Страница 43: ...Modbus communications over TCP IP is optional and requires configuration using the DeviceInstaller Software provided by Lantronix Inc Table 21 TCP IP Default Settings Setting Value IP Address 0 0 0 0...

Страница 44: ...number character bit 1 26 0x01A 27 0x01B Model Num 29_32 Model number character bit 1 28 0x01C 29 0x01D Watt Minutes High For Odometer bit 1 30 0x01E 31 0x01F Watt Minutes Low For Odometer bit 1 32 0x...

Страница 45: ...tate of alarm comms circuit board see Extended Status Bit Definition bit 1 128 0x080 129 0x081 Default Output Maximum Power Maximum rated power V Cell 32768 130 0x082 131 0x083 Default Output Maximum...

Страница 46: ...l 32768 180 0x0B4 181 0x0B5 Default Output Commissioning Duration Commissioning Duration Hr 3600 182 0x0B6 183 0x0B7 Default Output Commissioning A Commissioning Amps A 32768 184 0x0B8 185 0x0B9 Defau...

Страница 47: ...d power V Cell 32768 274 0x112 275 0x113 Output A Maximum Voltage Maximum rated voltage in x xx V V Cell 32768 276 0x114 277 0x115 Output A Maximum Current Maximum rated current in x xxA A 32768 278 0...

Страница 48: ...Output Rated Power Output Rated Power W 32768 330 0x14A 331 0x14B Output A Default Output Rated Current Output Rated Current A 32768 332 0x14C 333 0x14D Output A Periodic Boost Duration Periodic Boost...

Страница 49: ...ng Float Cell Voltage used in Program Mode V Cell 32768 424 0x1A8 425 0x1A9 Output B Program Boost Setting Boost Cell Voltage used in Program Mode V Cell 32768 426 0x1AA 427 0x1AB Output B Program Mod...

Страница 50: ...utput C Status Current State of the charger see section 11 3 Bits 1 498 0x1F2 499 0x1F3 Output C Alarms Alarm status bits see section 11 4 Bits 1 500 0x1F4 501 0x1F5 Output C Voltage Voltage currently...

Страница 51: ...rogram Mode Cells 32768 574 0x23E 575 0x23F Output C Program Temp comp slope In 0 xx C per output volt x 1 C V 32768 576 0x240 577 0x241 Output C Low DC Program Alarm setpoint for low DC used for Prog...

Страница 52: ...rrently being supplied by the charger to the battery A 32768 648 0x288 649 0x289 Output D Power Output Power currently being supplied by the charger W 32768 650 0x28A 651 0x28B Output D Factory Float...

Страница 53: ...Low Crank Program Alarm setpoint for low Crank used for Program Mode setting V Cell 32768 724 0x2D4 725 0x2D5 Output D Low Current Program Alarm setpoint for low Current used for Program Mode setting...

Страница 54: ...0x08 Reverse Polarity The charger is off due to a reverse polarity condition 9 0x09 Reserved For Future Use Reserved for Future Use 10 0x0A Low Battery Error Charger was not able to bring up a low ba...

Страница 55: ...available for future use reads false Off 0 25 0x19 Alarm Load Disconnect Load relay open set at end discharge clear when not on discharge 26 0x1A Alarm Individual Unit Fault Alarm flag 32 54 active fo...

Страница 56: ...003 Reset periodic battery check schedule ON to reset schedule OFF is no op 4 0x004 Clear battery check failure Default Output ON to reset alarm OFF is no op 5 0x005 Clear low cranking failure Default...

Страница 57: ...ttings install three jumpers on the charger to select the Battery Type Float Voltage and Range for your battery 103 Stand alone Charger Inconsistent jumper settings for chargers not used as modules Wh...

Страница 58: ...k for a module that has failed indicated by its LED status Check for disconnected or damaged SENSbus data cables Check for miswired disconnected or damaged input and output connections 203 Charger or...

Страница 59: ...to accessory display board cable failure 5 Failed accessory display board 1 Verify that a terminator is installed in port 1 or 2 of main power board J901 If terminator is missing install missing term...

Страница 60: ...ng setup utility as required SOLID GREEN SOLID RED AC good charger fail or overvoltage shutdown 1 Charger has experienced an unexpected fault 2 Programmed setting are incorrect OVSD set too low 3 Char...

Страница 61: ...63Hz or that 8VDC is present at DC output terminal block breaker and that the DC polarity is correct Correct charger AC input and DC output voltage as required 2 If step 1 doesn t resolve RED AC light...

Страница 62: ...y at AC input terminal block J100 are in the range 80VAC 264VAC 47Hz 63Hz or that 8VDC is present at DC output terminal block breaker and that the DC polarity is correct Correct charger AC input and D...

Страница 63: ...recharge batteries and ensure that all battery cells in a battery string are charged to the same level Boost see above and Equalize are often used synonymously however Equalize is employed most frequ...

Страница 64: ...23 1 21 27720 1 1 21 6 6 2 81 7 25 9 17 7 21 5 9 6 216 1 5 9 6 5 37 21 7 33529 1 7 5 6 56 0 16 216 72 5 1 6 3 5 60 6 67 6 7 2 6 67 1 5 56 5 9 2 80 17 180 5 6 6 5 37 21 1 0 7 5 1 7 5 1 352 7 21 81 66 2...

Страница 65: ...7720 1 1 21 6 6 2 81 7 25 9 17 7 21 7 6 9 6 6 2 1 7 237 21 5 3 6 1 5 02817 5 76 5 9 6 216 1 5 9 6 5 37 21 7 33529 1 7 5 6 56 0 16 216 72 5 1 6 3 5 60 6 67 6 7 2 6 67 1 5 56 5 9 2 80 17 180 5 6 6 5 37...

Страница 66: ...s full responsibility for continued compliance with the standard Product Name Battery Charger Model Name s MicroGenius S2 and S4 Presented to STORED ENERGY SYSTEMS LLC 1840 INDUSTRIAL CIRCLE CO 80501...

Страница 67: ...or facility which is contracted after the validity date of the ABS Rules and specifications used to evaluate the Product will require re evaluation of the PDA Use of the Product for non ABS classed v...

Страница 68: ...the product Type Approval does not necessarily waive witnessed inspection or survey procedures where otherwise required for products to be used in a vessel MODU or facility intended to be ABS classed...

Страница 69: ...of the laws of the Member States relating to the making available on the market of electrical equipment designed for use within certain voltage limits recast Directive 2011 65 EU of the European Parl...

Страница 70: ...be returned freight prepaid to the factory under a Return Material Authorization RMA number provided by SENS If in SENS opinion the problem can be rectified in the field SENS may elect to ship replac...

Отзывы: