SENS MicroGenius S2/S4 Technical Manual
53
Address High
Address Low
Name
Description
Units
Scale
678
0x2A6
679
0x2A7 Output D Battery Check
Interval
Interval between scheduled
automatic battery checks
Sec
1
680
0x2A8
681
0x2A9 Output D Number of
Chargers
Number of chargers detected on
SENSbus, 0 - 30
Num
1
682
0x2AA
683
0x2AB Output D Redundancy Level Number of redundant output
chargers
Num
1
684
0x2AC
685
0x2AD Output D Extended Status
Current state of alarm/comms circuit
board (see section 11.5)
bit
1
704
0x2C0
705
0x2C1 Output D Maximum Power Maximum rated power
V/Cell
32768
706
0x2C2
707
0x2C3 Output D Maximum
Voltage
Maximum rated voltage in x.xx V
V/Cell
32768
708
0x2C4
709
0x2C5 Output D Maximum
Current
Maximum rated current in x.xxA
A
32768
710
0x2C6
711
0x2C7 Output D Program Float
Setting
Float Cell Voltage used in Program
Mode
V/Cell
32768
712
0x2C8
713
0x2C9 Output D Program Boost
Setting
Boost Cell Voltage used in Program
Mode
V/Cell
32768
714
0x2CA
715
0x2CB Output D Program Mode
Mode callouts for Program Mode
setting (battery type… etc.)
Custom
1
716
0x2CC
717
0x2CD Output D Program Cell
Count
Number of cells set in Program Mode
Cells
32768
718
0x2CE
719
0x2CF Output D Program Temp
comp slope
In 0.xx°C per output volt x -1
°C/V
32768
720
0x2D0
721
0x2D1 Output D Low DC Program Alarm setpoint for low DC (used for
Program Mode setting)
V/Cell
32768
722
0x2D2
723
0x2D3 Output D Low Crank
Program
Alarm setpoint for low Crank (used
for Program Mode setting)
V/Cell
32768
724
0x2D4
725
0x2D5 Output D Low Current
Program
Alarm setpoint for low Current(used
for Program Mode setting)
A
32768
728
0x2D8
729
0x2D9 Output D High DC Program Alarm setpoint for high DC (used for
Program Mode setting)
V/Cell
32768
730
0x2DA
731
0x2DB Output D OVSD Program
Alarm setpoint for OVSD (used for
Program Mode setting)
V/Cell
32768
732
0x2DC
733
0x2DD Output D Batt Discharge
Program
Alarm setpoint for Batt Discharge
(used for Program Mode setting)
V/Cell
32768
734
0x2DE
735
0x2DF Output D Batt End
Discharge Program
Alarm setpoint for End Discharge
(used for Program Mode setting)
V/Cell
32768
736
0x2E0
737
0x2E1 Output D Program Boost
Time Limit
Boost time limit (used for Program
Mode setting)
Hr
3600
738
0x2E2
739
0x2E3 Output D Current Limit
Setting
Current Limit setpoint in % of output
current as a 10 bit value
% Rated
A
32768
740
0x2E4
741
0x2E5 Output D Default Output
Helix Float Time
Helix Float Time
Hr
3600
742
0x2E6
743
0x2E7 Output D Default Output
Helix Refresh Time
Helix Refresh Time
Hr
3600
744
0x2E8
745
0x2E9 Output D Default Output
Helix Eco Time
Helix Eco Time
Hr
3600
746
0x2EA
747
0x2EB Output D Default Output
Periodic Boost Time
Interval between scheduled Periodic
Boost
Days
86400
748
0x2EC
749
0x2ED Output D Battery Check
Voltage Setting
Battery check failure threshold
V/Cell
32768
750
0x2EE
751
0x2EF Output D Battery Check
Interval
Interval between scheduled
automatic battery checks
Days
86400
752
0x2F0
753
0x2F1 Output D Battery Check
Duration of battery check
Min
60