SENS EnerGenius® DC Wallbox Technical Manual
21
Pin 1
TWO PORTS:
Connect CANbus and/or
Modbus to one or both
ports
Pin 1
Pin 1
Figure 6
–
CANbus and RS-485 RJ-45 Connections
Table 10
–
Connector Pinout
Pin #
Purpose
1
CANbus
2
CANbus
3
No connect pass-through
4
Modbus
–
D0 (B)
5
D1 (A)
6
No connect pass-through
7
Power*
8
Common (isolated)
*Main circuit PCA only, used for interconnect between SENS devices
Figure 7
–
RJ-45 to Terminal Block Adapter
—
Optional
6.7.4.
Termination
For proper operation, a 120-ohm terminator is required at the ends of the CAN and/or RS-485
bus. If multiple devices are on the bus, only the devices on the ends of the network bus need
termination resistors. Figure 8 shows an example of how to terminate the network. Termination
may be provided as part of the network cabling or 120-ohm termination plugs for the RJ-45
communications connector on the charger are available to order separately (SENS p/n 803707).