SENS EnerGenius® DC Wallbox Technical Manual
39
type is changed. Delay affects all outputs
for multiple output models.
Auto-Boost
Enable or disable Dynamic Boost mode
Auto Boost Limit
Adjust the maximum amount of time
charger will be in Dynamic Boost mode
from 1 to 100 hours. The Boost time
limit is reset if charger power is cycled or
an engine crank is detected.
Boost Duration
Adjust amount of time charger will be in
scheduled periodic Boost mode from 1
to 100 hours. The Boost timer is reset if
charger power is cycled
Scheduled Boost
Adjust amount of time between periodic
scheduled Boost events from 1 to 180
days. Set to OFF to disable.
Run Timed Boost
Start or stop a manual Boost cycle. Will
operate in Boost mode until the Boost
Duration expires.
Output Settings
Float Voltage
Adjust output Float voltage, must be
greater than 60% of Boost setting
Boost Voltage
Adjust output Boost voltage from, must
be same or greater than Float setting,
must not be greater than 166% of Float
setting
HELIX-EcoFloat
Enable or disable HELIX mode
Current Rating
System current limit setting.
Set to “No
Limit Set” for full current capacity. Set a
value in amps to limit available current.
It is sometimes necessary to limit
maximum charging current to the
battery. This parameter allows the total
power from more than one module to
be adjusted to less than the full current
capability of all installed modules. In
case of a module failure, the remaining
module(s) would then each deliver
additional power, up to the limit of this
parameter, or up to each module’s
maximum rated output.
Temp. comp./°C
Adjust temperature compensation slope
from 0 to -0.30%V/°C
Alarms & Settings
Alarm Delay Time
Adjust amount of time to delay
activation of alarms after alarm event
takes place from 5 to 60 seconds.
Alarm/comms circuit board alarm relay
contacts and alarms on communications
ports are delayed; LED alarm indication
is not delayed.
Ground Fault Alarm
Enable or disable ground fault alarm.