SENS EnerGenius® DC Wallbox Technical Manual
24
6.9.3.
Remote Alarm/Communications Panel Accessory Connection
—
Optional
The optional remote alarm/communications panel accessory provides the ability to adjust and
communicate with multiple chargers using one external device. The remote panel accessory may
be configured with different alarm relay assignments than the alarm relays native to the charger.
Remove a factory installed 120-ohm terminator from the SENSbus RJ-45 port on the charger to
connect the network cable from the remote panel. Ensure a terminator remains in another
SENSbus RJ-45 port on the charger. Connect a straight-thru splitter to the RJ-45 SENSbus port on
the remote panel. Place a 120-ohm terminator in one of the positions on the remote panel
splitter to ensure a terminator is located at both ends of the communications bus. Connect the
remote panel to the charger using a network cable from the SENSbus RJ-45 port on the charger to
the remote panel splitter.
6.10.
Verify Connections
6.10.1.
Verify that all connections are secure and in the proper locations. Tighten all unused screws on
terminal blocks to secure them against vibration.
6.10.2.
Ensure all wires are routed in a way that the cover or other objects will not pinch or damage
them.