SENS EnerGenius® DC Wallbox Technical Manual
40
End Discharge
Adjust setpoint to trigger Battery End-of-
Discharge alarm, must be less than Low
DC setting
Low DC Voltage
Adjust setpoint to trigger Low DC voltage
alarm, must be greater than End
Discharge setting and less than Battery
Discharging setting
Batt Discharging
Adjust setpoint to trigger Battery
Discharging alarm, must be between
Low DC setting and 98% of Float setting
or Eco-Float setting when HELIX is active
High DC Voltage
Adjust setpoint to trigger High DC
voltage alarm, must be greater than
Boost by 2% of Float setting, must be
less than 40% higher than Boost setting
Overvolt Fault
Adjust setpoint to trigger Over Voltage
Shutdown alarm, must be greater than
High DC setting
Low Current
Adjust setpoint to trigger Low Current
alarm from 0% to 50% of nominal
current
Battery Set-up
Battery Select
(type)
Select type of battery to be charged -
flooded lead-acid, AGM, nickel-cadmium
VRLA, power supply.
Battery Select
(cells)
Adjust number of series cells in battery
string
Batt Commission
(voltage)
Adjust battery commissioning output
voltage must be greater than or equal to
Float voltage
Batt Commission
(current)
Adjust battery commissioning output
current from 5% to 100% of nominal
current rating
Batt Commission
(duration)
Adjust battery commissioning hours
from 1 to 120 hours
Batt Commission
(enable)
Start or stop commissioning cycle.
Charger will deliver commissioning
voltage and current until commissioning
hours expire.
DC Start Volts
Adjust DC Startup Voltage. Set to zero to
start into zero-volt battery
automatically.
Force Startup
Enables charger to attempt to charge a
battery with a voltage below the DC
Startup Voltage.
Restore Factory Default Settings
Restore settings to factory configuration
Other Settings
LCD Brightness
Adjust LDC Brightness from 0
–
100%
Minimum System Number of
Chargers
Enable or disable whether alarm is
indicated or not. Alarm active when the
number of charger modules active on