background image

ENGLISH - 7/8

MI004531-E

10 GND
11 A(+)
12 B (-)

10 GND
11 RX
12 TX

N.A.2=22

CO.2=23

N.C.2=24

N.A.1=19

CO.1=20

N.C.1=21

13 DI1

14 DI2

15 +12V

16 GND

17 DI3

18 DI4

0V

Max 24V

12V

 20mA

13 DI1

14 DI2

15 +12V

16 GND

17 DI3

18 DI4

13 DI1

14 DI2

15 +12V

16 GND

17 DI3

18 DI4

0V

5 AI1
6 AI2

1 +12V 

(*)

+12V

 40mA

4 GND
5 AI1
6 AI2

+

+

4 GND
5 AI1
6 AI2

+

+

2

1

3

+12V

 at 40 mA

Auxiliary volt.

Powersupply

Powersupply

19 – 28V

 50 – 60 Hz

 11 – 40V

   6.5W

Warning: When you turn On the module for the first time, the device must be supplied 
without any interruptions for at least 72 hours in order to charge the internal batteries
Power off the module, with the PS1 button, before connecting the inputs and outputs.
In order to satisfy the electromagnetic compliance requirements:
- Use shielded cables for the signals transmission.
- Connect the shield to a preferential ground for devices.
- Space the shielded cables from other cables used for power installations.
(transformers, inverters, motors, induction ovens, etc...).

 POWERSUPPLY

The power supply must be connected to terminals 2 and 3.
The supply voltage must be between:
19 and 40V

 

(any polarity), or between 19 and 28 V

.

The upper limits must not be exceeded in order to avoid serious
damage to the module. 
The power supply source must be protected from 
any malfunctions of the module through appropriately sized safety fuse.

 TWO ANALOG INPUTS

Voltage

Current active sensor (4 wires) Current passive sensor (2 wires) The module has two

software voltage or
current configurable
analog inputs.
For the configuration
software you can read
the user manual.

 FOUR DIGITAL INPUTS

Internal power supply NPN

Internal power supply PNP

External power supply PNP

 TWO DIGITAL OUTPUTS

The module has two digital 
outputs with free contacts.
The figures show the internal relay 
contacts available.

 COM2 SERIAL PORT

RS485

SERIAL

PORT

(SW2=OFF

)

RS232

SERIAL

PORT

(SW2=ON

)

The module has a serial port 
available to terminals 10-11-12 
You can configure this port 
through SW2 switch.

ELECTRICAL CONNECTIONS

(*) Not available without

 external powersupply 

19

Содержание Z-LOGGER3

Страница 1: ...ed in it This informations may be modified or integrated for technical and or commercial requirements SENECA s r l Headquarters Via Austria 26 35127 PADOVA ITALY Phone 39 049 8705355 8705359 Fax 39 04...

Страница 2: ...F Network Searching or Missing Signal OFF Modem OFF LED SIGNALING ON FRONT PANEL Dimensions L H W 35 x 100 x 111 mm with terminals Weight 250 g Case Material PA6 black color 100 mm Z UMTS Connector Re...

Страница 3: ...4 Energized 12V closed contact OFF Digital Input 4 De energized open contact PWR STS Green ON Z UMTS ON inactive log status ready Slow Blinking 2 8 sec ON 0 4 sec OFF Z UMTS active log status normal S...

Страница 4: ...argeable batteries CONNECTIONS Removable three pole screw terminal pitch 5mm 2 for cable up to 2 5 mm rear IDC10 front RJ45 Micro USB and Antenna SMA POWERSUPPLY Voltage Power absorbed 19 40 V or 19 2...

Страница 5: ...ure 40 C and one of the severe operating condition exists The operating temperature 35 C and two of the severe operating conditions exist Disposal of electrical electronic equipment applicable through...

Страница 6: ...C10 connector into a free slot of DIN rail accessory as you can see in fig 1a the insertion is one way only because the connectors are polarized 3 To secure the module to the IEC EN 60715 DIN rail tig...

Страница 7: ...lations transformers inverters motors induction ovens etc POWERSUPPLY The power supply must be connected to terminals 2 and 3 The supply voltage must be between 19 and 40V any polarity or between 19 a...

Страница 8: ...ETH USB The module has a RJ45 socket on frontal panel Note Inserting the RJ45 10 100 Base T Ethernet plug make sure that the connector is securely latched or before inserting the cable into the RJ45...

Отзывы: