ENG
Service settings manual
35
Table with description of parameters :
Para-
meter
Function
Parameter description
Setting range
Default
value
W1.1 HEAT METERING
With this setting we turn on the system which measures
acquired solar energy.
0- NO
1- YES
0
W1.2 MEDIUM
Select transfer medium in the solar system.
0- WATER
1- PROPYLENGLYCOL
2- ETHYLENGLYCOL
3- TYFOCOR
4- TYFOCOR LS, G-LS
5- THESOL
0
W1.3 GLYCOL
MIXTURE
Set the glycol concentration.
By Tyfocor LS and G-LS this setting has no effect.
10 ÷ 100 %
40
W1.4 HOT
SENSOR
Select the sensor which is in collectors.
1- T1 (T3) 2- T2
3- T3 4- T4
5- T5 6- T6
1
W1.5 COLD
SENSOR
Select the sensor Tc which is on the return pipe into
collectors.
1- T1 2- T2
3- T3 4- T4
5- T5 6- T6
7- T7
7
W1.6 FLOW
METER
With settings you define whether there is a built-in flow
meter.
0- NO
1- YES
0
W1.7
IMPULSE RATE OF
FLOW METER
You insert characteristic data of flow meter - amount od
volume per impulse.
0,5 ÷ 25 l/imp
1
W1.8
FLOW IN FIRST COL-
LECTOR FIELD
If you do not use the flow meter, read out and set flow
from the mechanic flow meter in first collector field when
the pump is running at 100 %.
1 ÷ 100 l/min
6
W1.9
FLOW IN SECOND
COLLECTOR FIELD
If you do not use the flow meter, read out and set flow
from the mechanic flow meter in second collector field
when the pump is running at 100 %.
1 ÷ 100 l/min
6
W1.10 FLOW IN FIRST AND
SECOND COLLECTOR
FIELD
If you do not use the flow meter, read out and set flow
from the mechanic flow meter for both collector fields
when both pumps are running at 100 %.
This setting is used only by schems where both collector
fields can operate simultaneously.
2 ÷ 100 l/min
12
W1.11 MIN. SOLAR POWER
TO SWITCH-OFF AUX.
HEAT SOURCES
Setting of solar collector power output, by which the
auxiliary heat sources should switch-off.
REMARK: This function is possible only if energy measu-
rement is activated and at least one auxiliary heat source
is selected.
1 ÷ 20 kW
10
W1.12 OUTPUTS SWITCHED
OFF AT MIN. SOLAR
POWER
Selection of auxiliary heat sources which should switch-
off if solar system exceeds setted power output.
0- NONE
1- R1
2- R3
3- R1, R3
0