2 - MANUAL MODE
changeover of zone concerned to manual mode, during which the manual mode selected will be constantly maintained
Continuous day temp:
permanently maintained daytime temperature mode selected
Continuous night temp:
permanently maintained nighttime temperature mode selected
Custom temp:
permanently maintained custom set temperature mode selected
Antifrost:
permanently maintained frost protection temperature mode selected
Remote mode:
selecting remote control mode, during which the signal sent to remote control input (open/close contact) turns burner/radiator on or off (to
correct operation set operational logic of remote control)
Chimney-sweep:
selects timed mode to measure burners/radiators, during which burners/radiators will permanently be turned on
3 - ZONE TURN OFF
turns off the heating of given zone
4 - WEEKLY TIME PROGRAM
setting weekly time program of zone in automatic mode in a simple, transparent graphical manner. On 24 hours’ continuum of numbers, blue
colour means night time temperature, red corresponds to daytime temperature. Here you can consult, modify, delete or create red domains to develop daily temperature
programs, as required.
Change:
modification of actual red domain period (red domains will automatically be blended, if overlapping occurred)
Add:
creates new red domain for actual day
Delete time interval:
deletes actual red domain
Delete whole day:
deletes all red domains for actual day
Delete whole week:
deletes all red domains for all days of zone
Copy day to day:
copies actual daily time program to another day within zone, by overwriting (e.g. copy Monday of Zone1 to Tuesday of Zone1)
Copy day to zone:
copies actual daily time program to the same day of another zone, by overwriting (e.g. copy Monday of Zone1 to Monday of Zone2)
Copy week to zone:
copies whole weekly time program to another zone, by overwriting (e.g. copy all days Zone1 into Zone2)
5 - HOLIDAYS
setting holiday periods in automatic mode of zone. During periods set, the holiday temperature will be maintained in automatic mode.
6 - TEMPERATURES
setting temperatures
Day temp:
setting daytime temperature to be used in automatic mode and as perm. daytime temperature in manual mode
Night temp:
setting nighttime temperature to be used in automatic mode and as perm. nighttime temperature in manual mode
Holiday temp:
setting holiday time temperature to be used in automatic mode during holiday periods
Antifrost temp:
setting
defrosting
temperature to be used in frost protecting manual mode (neither daytime, nor nighttime nor holiday temperatures will be
allowed to be lower than the temperature set here)
Remote min.temp:
setting minimal zone temperature of remote mode; below this temperature level the heating forced to start unconditionally
Remote max.temp:
setting maximal zone temperature of remote mode; above this temperature level the heating forced to stop unconditionally
7 - TEMPERATURE OPTIMIZATION
enabling temperature optimisation function, causing that in automatic mode the change between nighttime and daytime modes will be
performed earlier than set in weekly time schedule, so as to reach daily temperature of zone to desired time (the temperature optimisation function can only be used
when external heat sensor installed within system)
8 - INNER-SENSOR CORRECTION
setting temperature correction caused by the location where internal heat sensor of zone installed; the value set here shall be
deducted/added from/to real temperature measured by heat sensor
9 - HYSTERESIS
setting switching hysteresis of burner/radiator
1
st
stage hysteresis:
switching hysteresis of stage1. of burner/radiator (see fig. 8.)
2
nd
stage delta-T:
switching hysteresis of stage2. of burner/radiator (see fig. 8.)
10 - TIMINGS
settings of turning ons and offs of burner/radiator
Burner min.worktime:
sets minimum operating time of burner (see fig. 8.)
2
nd
stage delay:
sets delayed start of stage 2. after startup of burner (see fig. 8.)
Ventilator on delaying:
sets delayed start of fan after startup of burner (see fig. 8.)
Ventilator off delaying:
setting delayed stop of fan after shut-off of burner (see fig. 8.)
Ventilator min.stoptime:
setting minimal idle time of fan after shut-off (see fig. 8.)
11 - REMOTE WORKING LOGIC
setting contact definition set to remote control input
NC=heat:
short-circuiting of remote control input turns heating on, removal of input short-circuit turns heating off in remote controlled manual mode
NC=no heat:
short-circuiting of remote control input turns heating off, removal of input short-circuit turns heating on in remote controlled manual mode
12 - BURNER TYPE
setting stage numbers of burner
One staged:
means one-stage burner/radiator
Two staged:
means double stage burner/radiator (burner starts up by starting stage 1, then after a delay, the second stage will also be started)
13 - BURNER RESET MODE
setting ACK method of burner/radiator
Send reset signal:
the controller sends a reset-signal to burner for a short time (can be used if there is a reset nput connected to burner)
1 minute powerloss:
the controller switches off burner for a short time, then, if necessary restarts it (can be used in the case if there is no reset input on burner or it
is disposing of but not being connected to)
14 - BURNER POWER
setting burner power (used to consumption data calculation)
1
st
stage:
means the power of burner for one-stage burner and that of first stage for double stage burner
Both stages:
total power of double stage burner (shall only be given in case of double stage burner)
15 - ZONE DESCRIPTION
setting zone designation (in main screen will be added to zone number, if indicated)
16 - ZONE BUSMODULE#
used only with bus system
17 - TOTAL WORKING HOURS
display of total operating time of burner/radiator of zone (at double stage burner in brackets the number of operating hours in double stage
mode)
18 - PARTIAL WORKING HOURS
display of operating time since last resetting of burner/radiator of zone (the partly counter is similar to total operating hours’ meter, but this
one can be used as partly counter which can be reset)
19 - PARTIAL COSTS
fuel consumption costs of zone since last resetting (a correct value can only be expected if following parameters correctly set: currency, energy costs,
burner type, burner power)
20 - YEARLY COSTS
display of fuel consumption costs of zone since last years saved by the controller (a correct value can only be expected if following parameters correctly
set: currency, burner type, burner power and energy costs monthly readjusted)
21 - MONTHLY COSTS
display of monthly costs of fuel consumption of zone since last years saved by the controller (a correct value can only be expected if following
parameters correctly set: currency, burner type, burner power and energy costs monthly readjusted)
14