EN

2 - MANUAL MODE

 changeover of zone concerned to manual mode, during which the manual mode selected will be constantly maintained

Continuous day temp:

permanently maintained daytime temperature mode selected

Continuous night temp:

permanently maintained nighttime temperature mode selected

Custom temp:

permanently maintained custom set temperature mode selected

Antifrost:

permanently maintained frost protection temperature mode selected

Remote mode:

selecting remote control mode, during which the signal sent to remote control input (open/close contact) turns burner/radiator on or off (to 
correct operation set operational logic of remote control)

Chimney-sweep:

selects timed mode to measure burners/radiators, during which burners/radiators will permanently be turned on

3 - ZONE TURN OFF

 turns off the heating of given zone

4 - WEEKLY TIME PROGRAM

 setting weekly time program of zone in automatic mode in a simple, transparent graphical manner. On 24 hours’ continuum of numbers, blue 

colour means night time temperature, red corresponds to daytime temperature. Here you can consult, modify, delete or create red domains to develop daily temperature
programs, as required.
Change:

modification of actual red domain period (red domains will automatically be blended, if overlapping occurred)

Add:

creates new red domain for actual day

Delete time interval:

deletes actual red domain

Delete whole day:

deletes all red domains for actual day

Delete whole week:

deletes all red domains for all days of zone

Copy day to day:

copies actual daily time program to another day within zone, by overwriting (e.g. copy Monday of Zone1 to Tuesday of Zone1)

Copy day to zone:

copies actual daily time program to the same day of another zone, by overwriting (e.g. copy Monday of Zone1 to Monday of Zone2)

Copy week to zone:

copies whole weekly time program to another zone, by overwriting (e.g. copy all days Zone1 into Zone2)

5 - HOLIDAYS

 setting holiday periods in automatic mode of zone. During periods set, the holiday temperature will be maintained in automatic mode.

6 - TEMPERATURES

 setting temperatures

Day temp:

setting daytime temperature to be used in automatic mode and as perm. daytime temperature in manual mode

Night temp:

setting nighttime temperature to be used in automatic mode and as perm. nighttime temperature in manual mode

Holiday temp:

setting holiday time temperature to be used in automatic mode during holiday periods

Antifrost temp:

setting 

defrosting

 temperature to be used in frost protecting manual mode (neither daytime, nor nighttime nor holiday temperatures will be 

allowed to be lower than the temperature set here)

Remote min.temp:

setting minimal zone temperature of remote mode; below this temperature level the heating forced to start unconditionally

Remote max.temp:

setting maximal zone temperature of remote mode; above this temperature level the heating forced to stop unconditionally

7 - TEMPERATURE OPTIMIZATION

 enabling temperature optimisation function, causing that in automatic mode the change between nighttime and daytime modes will be 

performed earlier than set in weekly time schedule, so as to reach daily temperature of zone to desired time (the temperature optimisation function can only be used 
when external heat sensor installed within system)

8 - INNER-SENSOR CORRECTION

 setting temperature correction caused by the location where internal heat sensor of zone installed; the value set here shall be 

deducted/added from/to real temperature measured by heat sensor

9 - HYSTERESIS

 setting switching hysteresis of burner/radiator

1

st

 stage hysteresis:

switching hysteresis of stage1. of burner/radiator (see fig. 8.)

2

nd

 stage delta-T:

switching hysteresis of stage2. of burner/radiator (see fig. 8.)

10 - TIMINGS

 settings of turning ons and offs of burner/radiator

Burner min.worktime:

sets minimum operating time of burner (see fig. 8.)

2

nd

 stage delay:

sets delayed start of stage 2. after startup of burner (see fig. 8.)

Ventilator on delaying:

sets delayed start of fan after startup of burner (see fig. 8.)

Ventilator off delaying:

setting delayed stop of fan after shut-off of burner (see fig. 8.)

Ventilator min.stoptime:

setting minimal idle time of fan after shut-off (see fig. 8.)

11 - REMOTE WORKING LOGIC

 setting contact definition set to remote control input

NC=heat:

short-circuiting of remote control input turns heating on, removal of input short-circuit turns heating off in remote controlled manual mode

NC=no heat:

 short-circuiting of remote control input turns heating off, removal of input short-circuit turns heating on in remote controlled manual mode

12 - BURNER TYPE

 setting stage numbers of burner

One staged:

means one-stage burner/radiator

Two staged:

means double stage burner/radiator (burner starts up by starting stage 1, then after a delay, the second stage will also be started)

13 - BURNER RESET MODE

 setting ACK method of burner/radiator

Send reset signal:

the controller sends a reset-signal to burner for a short time (can be used if there is a reset nput connected to burner)

1 minute powerloss:

the controller switches off burner for a short time, then, if necessary restarts it (can be used in the case if there is no reset input on burner or it
is disposing of but not being connected to)

14 - BURNER POWER

 setting burner power (used to consumption data calculation)

1

st

 stage:

means the power of burner for one-stage burner and that of first stage for double stage burner

Both stages:

total power of double stage burner (shall only be given in case of double stage burner)

15 - ZONE DESCRIPTION

 setting zone designation (in main screen will be added to zone number, if indicated)

16 - ZONE BUSMODULE#

 used only with bus system

17 - TOTAL WORKING HOURS

 display of total operating time of burner/radiator of zone (at double stage burner in brackets the number of operating hours in double stage 

mode)

18 - PARTIAL WORKING HOURS

 display of operating time since last resetting of burner/radiator of zone (the partly counter is similar to total operating hours’ meter, but this 

one can be used as partly counter which can be reset)

19 - PARTIAL COSTS

 fuel consumption costs of zone since last resetting (a correct value can only be expected if following parameters correctly set: currency, energy costs, 

burner type, burner power)

20 - YEARLY COSTS

 display of fuel consumption costs of zone since last years saved by the controller (a correct value can only be expected if following parameters correctly 

set: currency, burner type, burner power and energy costs monthly readjusted)

21 - MONTHLY COSTS

 display of monthly costs of fuel consumption of zone since last years saved by the controller (a correct value can only be expected if following 

parameters correctly set: currency, burner type, burner power and energy costs monthly readjusted)

14

Содержание EVO1

Страница 1: ...lation Manual Important Notice 3 Type Variants 3 Frontpanel 4 Control Board 4 Connecting Power Up 5 Software Settings 8 Software Main Screen 8 Software Main Menu 9 Software Zone Menu 12 List of Parameters 15 Technical data 15 Index 16 ...

Страница 2: ...EVO SZUTM_A5B010AEN Fig 1 Fig 2 Fig 3 ...

Страница 3: ...all be handed over to the applicable collection point By ensuring of this product is disposed correctly you will help prevent potential negative consequences for the environment and human health Recycling materials helps preserve resources of the earth TYPE VARIANTS EVO1 heating controller unit for one zone FUNCTIONS industrial temperature controller unit for several types of burners controlling o...

Страница 4: ...connections can easily be performed by using dismantling terminal blocks and terminal block functions marked on panel by pictures if possible You shall not leave the box cover hanging on the flat multicore cable in any case When installing you shall provide a support to the box cover or have it removed by disconnecting the easily dismantling line terminals 1 TERMINAL BLOCKS see their detailed desc...

Страница 5: ... phase output switched by Stage1 relay in case of a single stage burner or radiator the phase wire of burner radiator shall be connected here in case of a double stage burner or radiator the phase wire of first stage of burner radiator shall be connected here Stage2 output phase output switched by Stage2 relay in case of a single stage burner or radiator it is not in use shall be left free in case...

Страница 6: ...en the possibility to use Optimisation heating up mode Connection of auxiliary panel You shall exclusively use auxiliary panels which being compatible with EVO control unit information thereof can be obtained in the description of complementary panel Insert complementary panel into 10 pin serial connector of control unit as shown in figure Fig 2 and check then correctness of connection Power up th...

Страница 7: ...EN 7 Fig 5C Connection of Terminal Blocks EVO3 Fig 5D Connection of Terminal Blocks EVO4 ...

Страница 8: ...idays during both optimisation heating up and overtime heating up the remaining duration will be displayed In case of manual mode the manual mode type selected will be displayed 4 INNER TEMPERATURE the temperature measured within zone will be displayed 5 OUTTER TEMPERATURE displays the temperature measured by outside heat sensor of system if mounted 6 KEY SYMBOL displays actual access level which ...

Страница 9: ...setting date time language etc which are not in close relationship with individual heating zones Zone settings can be performed from zone menu according to Chapter Zone menu The figure shows the structure of main menu system Fig 6 and accessibility of each setting The description of numbered menu points can be found below figure 9 Fig 6 Main Menu System page1 ...

Страница 10: ...ncy to display zone costs 8 ENERGY COST unit price of energy calculated from fuel price and specific heat EUR kWh Calculation for oil unit price of oil EUR kg caloric power MJ kg 3 6 MJ kWh Calculation for gas unit price of gas EUR m3 caloric power MJ m3 3 6 MJ kWh 9 LANGUAGE SELECTION setting of controller language 10 PC KEYBOARD setting the layout of PC keyboard to be connected 11 KEYBOARD BEEP ...

Страница 11: ... notofication there will be no alert when service date reached Message notification when service time reached an alert box will be opened periodically to alert to service needed Message sound notification when service time reached there is an acoustic sound together with opening alert box 18 OUTTER SENSOR setting whether an external thermal sensor connected to system or not 19 OUTTER SENSOR CORREC...

Страница 12: ...between zones without leaving menu which enables significantly quicker setting of zones or inspection zone settings Miscellaneous other general settings which are relating to controller unit or to the whole of heating system can be carried out in main menu according to Chapter Main menu The structure of zone menu system can be seen in figure Fig 7 together with accessibility of individual settings...

Страница 13: ...to consideration during which holiday temperature is permanently maintained When temperature optimisation function set night time temperature can earlier be changed against daytime temperature than set in weekly time program optimised heating up mode so as to reach daytime temperature in desired time In night time mode one hour of daytime temperature period can be requested by actuating push butto...

Страница 14: ...8 INNER SENSOR CORRECTION setting temperature correction caused by the location where internal heat sensor of zone installed the value set here shall be deducted added from to real temperature measured by heat sensor 9 HYSTERESIS setting switching hysteresis of burner radiator 1st stage hysteresis switching hysteresis of stage1 of burner radiator see fig 8 2nd stage delta T switching hysteresis of...

Страница 15: ...age 2 10 00 600 00 sec 14 tvondelay Delay time of fan start 0 00 10 00 sec 15 tvoffdelay Delay time of fan shut off 0 00 20 00 min 16 tvoffmin Minimal idle time of fan 10 00 600 00 sec 17 Burner power in stage 1 0 50 1000 00 kW 18 Total burner power 0 50 1000 00 kW 19 Correction of internal clock 22 20 22 20 sec day Table 1 List of Parameters TECHNICAL DATA Description of product EVO1 heating cont...

Страница 16: ...ard beep Language selection Mainmenu 9 Settings Language keyboard Language selection Login Mainmenu 23 Login Monthly costs Zonemenu 21 Zone info Costs Monthly costs Night temp Zonemenu 6 Settings Temperatures Night temp Notification Mainmenu 17 Service menu Servicing datas Next servicing Notification Outter sensor Mainmenu 18 Service menu Misc settings Outter sensor Outter sensor correction Mainme...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Отзывы: