![Selbit ISP-12F Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/selbit/isp-12f/isp-12f_manual-handbook_1236443017.webp)
www.selbit.pl
- 17 -
For any additional information, please refer to the operating instructions of the ATV
320 converter manufacturer.
After fine-tuning of the parameters and checking the correctness of the operation of the
adjuster cooperating with the converter, save the configuration made to the ATV 320
memory so that it can be quickly restored if necessary.
Custom settings should be saved in the converter memory in configuration number 2(Str2
–
CFG2)
Configuration number 1(CFG1) contains pre-set settings supporting the ISP-12F adjuster
but does not contain drive parameter values; it is only used for the initial configuration.
Saving your custom configuration in the converter memory (Str2):
rdy – ConF – FCS –
Function
Value
Description of the function
Fry-
ALL
When the message ALL is displayed, press the knob so that the two
vertical bars on the right side of the display are displayed at the top
and then press ESC
SCSI
Str2
Selected configuration set number 2. Press the knob and hold for> 3s
until the dots on the display stop flashing
The configuration that is currently loaded into the converter cannot be selected for
saving. For example, if the converter is currently operating using the configuration
number 1, then you can only select configuration number 2 or restore factory settings
(InI).
Recovering a previously saved configuration from the machine's memory, (CFG2):
rdy – ConF – FCS –
Function
Value
Description of the function
FCSI
CFG2
Selected restore factory configuration
Fry-
ALL
When the message ALL is displayed, press the knob so that the two
vertical bars on the right side of the display are displayed at the top
and then press ESC
GFS
YES
After changing the message to YES, press and hold the knob for > 2s
until the dots on the display stops flashing
If the converter is supplied with the ISP-12F adjuster, you can restore the initial
configuration as described above by selecting the CFG1 name in the FCSI function.
Restoring factory settings of the ATV 320 converter
If necessary, you can restore the factory settings (it does not include the initial
configurations for the ISP-12F adjuster)
After restoring the factory settings, set all the required parameters according to the
operating instructions!