The SEL-2664S is generally applied to single generators
with high-resistance grounded neutral as shown in

Figure 8

 through 

Figure 12

. Similarly, it can also be

applied to a parallel generators configuration if only one
of the generators is grounded (e.g., cross-compound
generators).

For two generators connected in parallel, each with high-
resistance grounded neutral but sharing a common step-

up transformer, you can use two SEL-2664S Relays
(see

Figure 13

), and follow the special considerations and

limitations described in the 

SEL-2664S Instruction

Manual

 for such a configuration.

Figure 13

Parallel Generators Configuration—AC Connections Using Two SEL-2664S Relays

See 

Figure 14

 for a typical example of the dc connections

for 100 percent stator ground protection using the
SEL-2664S Stator Ground Protection Relay (stator-to-
ground insulation resistance measurement) and the
SEL-2664 Field Ground Module (dc field-to-ground
insulation resistance measurement).

Figure 14

Typical DC Connections for an SEL-2664S 

Application

NGR2

NGT2

CTN2A

VN

NN

X2

Generator 2

Generator 1

X1

CTN2B

CTN1B

 of

SEL-2664S-2

To

CO1

To

CO2

 of

SEL-2664S-2

To

CO1

To

CO2

Generator Relay

(if used)

VN

NN

NGR1

CTN1A

X1 X2

NGT1

IN

D02/VN

D01/NN

C02
C01

SEL-2664S-1

2-C twisted pair (preferably shielded) 

Do not ground the CTN leads.

I_SRC

IN

D02/VN

D01/NN

C02

C01

SEL-2664S-2

To

CTN1B

& CTN2B

I_SRC

52G1

52G2

WYE

GSU XFMR

DELTA

Generator Relay

(if used)

A11

A10 IN01

AO1

AO2

AO3

Alarm

Self Test/Status

SEL

-2

664S

43AMP

ON

Fiber-Optic Cable 

With ST Connectors 

From SEL-2664

RX

TX

Port 2

A04

A05

Trip 86G 

or

 Ground Fault Alarm

+/H
BO1

BO2

–/N

-DC

+DC

OUT02

GND

OUT01

Содержание SEL-2664S

Страница 1: ...ge elements Operator Controls Take advantage of multiple methods for accessing and using the operator interface of the relay The front and side panels have eight LEDs that indicate the ENABLED TRIP WA...

Страница 2: ...imple Network Time Protocol SNTP File Transfer Protocol FTP Telnet SEL ASCII SEL protocols including MIRRORED BITS communications Conformally Coated Overview Figure 1 Functional Diagram Operator Inter...

Страница 3: ...of the 64S elements described previ ously The combination of the two with their over lapping coverage provides 100 percent stator winding protection 100 percent of the time Neutral Ground Resistor Mo...

Страница 4: ...ry and Primary reference the Neutral Grounding Transformer NGT not CTN b Neutral current A sec is shown if CTN_LOC SEC otherwise it is hidden Table 1 Metered Quantities Sheet 2 of 2 Quantities Descrip...

Страница 5: ...ction or control schemes with eight general purpose SELOGIC control equa tion timers Each timer has independent time delay pickup and dropout settings Program each timer input with any element you nee...

Страница 6: ...ickSet in the following ways Develop settings offline with an intelligent settings editor that only allows valid settings Create SELOGIC control equations with a drag and drop text editor Configure pr...

Страница 7: ...under 26 V peak If a generator produces VN3 above this level even under normal load conditions the injection signal stops disabling the 64S elements However 59N1 59NRMS and 64F elements continue to pr...

Страница 8: ...for protection using redundant relays shown with neutral CTs on the secondary side of the neutral grounding transformer This application requires Relay 1 to set the Injection Source Mode setting MODE_...

Страница 9: ...for a typical example of the dc connections for 100 percent stator ground protection using the SEL 2664S Stator Ground Protection Relay stator to ground insulation resistance measurement and the SEL...

Страница 10: ...SEL 2664S Data Sheet Schweitzer Engineering Laboratories Inc 10 Relay Mounting and Dimensions Figure 15 SEL 2664S Wall Mount Dimensions Figure 16 SEL 2664S Connection Diagram for Wall Mount Option...

Страница 11: ...Engineering Laboratories Inc SEL 2664S Data Sheet 11 Figure 17 SEL 2664S Panel Mount Dimensions Figure 18 SEL 2664S Connection Diagram for Rack and Panel Mount Options Figure 19 SEL 2664S Rack Mount...

Страница 12: ...C Injection Source Connections Port 3 EIA 232 Serial Port Terminal C Neutral Current IN Connections Terminal B Power Supply 125 250 Vdc or 110 240 Vac Port 2 Fiber Optic EIA 232 Serial Port Terminal A...

Страница 13: ...40 Hz Maximum Open Terminal Voltage 26 V peak Protection Self protecting Power Supply Relay Start Up Time Approximately 5 10 seconds after power is applied until the ENABLED LED turns on High Voltage...

Страница 14: ...Telnet SNTP IEC 61850 MIRRORED BITS Operating Temperature IEC Performance Rating per IEC EN 60068 2 1 and 60068 2 2 40 to 85 C 40 to 185 F Not applicable to UL applications Operating Environment Insul...

Страница 15: ...mm2 14 AWG 2 1 mm2 Potential Voltage VN 16 AWG 1 3 mm2 10 AWG 5 26 mm2 Contact I O 18 AWG 0 8 mm2 14 AWG 2 1 mm2 a For all connection types the insulation voltage must be 300 V minimum Dielectric Str...

Страница 16: ...Ground 64S Pickup Range OFF 0 1 k 10 k primary Pickup Measurement Accuracy Steady State 10 of pickup 50 for pickup 2 k 15 pickup for 2 k pickup 10 k Time Delay Range 0 1 400 0 seconds Time Delay Accur...

Отзывы: