SEL- 2664S Data Sheet

 7

The following features of QuickSet monitor, commission,
and test the SEL-2664S.

The PC interface remotely retrieves power system
data.

The HMI monitors meter data, Relay Word bits,
and output contacts status during testing. The
control window allows resetting of diagnostics, and
targets.

The Firmware Loader in the Tools menu helps you 
upgrade the firmware.

Applications

The SEL-2664S is intended for high-resistance grounded
generator applications and cannot be used with low-
impedance-grounded, solidly grounded, and ungrounded
configurations. See 

Application Considerations

 in the

SEL-2664S Instruction Manual 

for additional details.

You can use the SEL-2664S to provide protection at
standstill and online with most typical levels of third-
harmonic voltage (VN3). The injection-based function of
the SEL-2664S requires that VN/NN terminal voltage
remains under 26 V peak. If a generator produces VN3
above this level, even under normal load conditions, the
injection signal stops, disabling the 64S elements.
However, 59N1, 59NRMS, and 64F elements continue to
protect the generator, and 64S elements are immediately
restored when VN3 drops below the safe level. Because
high VN3 indicates there is no ground fault near neutral,
the disabling of 64S elements has an insignificant impact
on protection.

If you want to avoid disabling 64S elements, the
SEL-2664S can be configured to inject a signal at an
NGR Tap. See 

Figure 7

 for basic ac connections using the

NGR Tap.

Figure 7

Basic AC Connections Using the NGR Tap

Figure 8

 and 

Figure 9

 show the ac connections for the

SEL-2664S with the neutral CT on the secondary side of
the neutral grounding transformer.

Figure 8

AC Connections With Neutral CT on the 

Secondary Side of the Neutral Grounding Transformer

IN

TAP %
NGR

NGT

CTN

D02/VN

D01/NN

C02

C01

SEL-2664S

2-C Twisted Pair. 
Do not ground the 
CTN leads.

I_SRC

100%

X1 X2

IN

NGR

NGT

CTN

D02/VN

D01/NN

C02

C01

SEL-2664S

2-C Twisted Pair. 
Do not ground the 
CTN leads.

I_SRC

X1 X2

Содержание SEL-2664S

Страница 1: ...ge elements Operator Controls Take advantage of multiple methods for accessing and using the operator interface of the relay The front and side panels have eight LEDs that indicate the ENABLED TRIP WA...

Страница 2: ...imple Network Time Protocol SNTP File Transfer Protocol FTP Telnet SEL ASCII SEL protocols including MIRRORED BITS communications Conformally Coated Overview Figure 1 Functional Diagram Operator Inter...

Страница 3: ...of the 64S elements described previ ously The combination of the two with their over lapping coverage provides 100 percent stator winding protection 100 percent of the time Neutral Ground Resistor Mo...

Страница 4: ...ry and Primary reference the Neutral Grounding Transformer NGT not CTN b Neutral current A sec is shown if CTN_LOC SEC otherwise it is hidden Table 1 Metered Quantities Sheet 2 of 2 Quantities Descrip...

Страница 5: ...ction or control schemes with eight general purpose SELOGIC control equa tion timers Each timer has independent time delay pickup and dropout settings Program each timer input with any element you nee...

Страница 6: ...ickSet in the following ways Develop settings offline with an intelligent settings editor that only allows valid settings Create SELOGIC control equations with a drag and drop text editor Configure pr...

Страница 7: ...under 26 V peak If a generator produces VN3 above this level even under normal load conditions the injection signal stops disabling the 64S elements However 59N1 59NRMS and 64F elements continue to pr...

Страница 8: ...for protection using redundant relays shown with neutral CTs on the secondary side of the neutral grounding transformer This application requires Relay 1 to set the Injection Source Mode setting MODE_...

Страница 9: ...for a typical example of the dc connections for 100 percent stator ground protection using the SEL 2664S Stator Ground Protection Relay stator to ground insulation resistance measurement and the SEL...

Страница 10: ...SEL 2664S Data Sheet Schweitzer Engineering Laboratories Inc 10 Relay Mounting and Dimensions Figure 15 SEL 2664S Wall Mount Dimensions Figure 16 SEL 2664S Connection Diagram for Wall Mount Option...

Страница 11: ...Engineering Laboratories Inc SEL 2664S Data Sheet 11 Figure 17 SEL 2664S Panel Mount Dimensions Figure 18 SEL 2664S Connection Diagram for Rack and Panel Mount Options Figure 19 SEL 2664S Rack Mount...

Страница 12: ...C Injection Source Connections Port 3 EIA 232 Serial Port Terminal C Neutral Current IN Connections Terminal B Power Supply 125 250 Vdc or 110 240 Vac Port 2 Fiber Optic EIA 232 Serial Port Terminal A...

Страница 13: ...40 Hz Maximum Open Terminal Voltage 26 V peak Protection Self protecting Power Supply Relay Start Up Time Approximately 5 10 seconds after power is applied until the ENABLED LED turns on High Voltage...

Страница 14: ...Telnet SNTP IEC 61850 MIRRORED BITS Operating Temperature IEC Performance Rating per IEC EN 60068 2 1 and 60068 2 2 40 to 85 C 40 to 185 F Not applicable to UL applications Operating Environment Insul...

Страница 15: ...mm2 14 AWG 2 1 mm2 Potential Voltage VN 16 AWG 1 3 mm2 10 AWG 5 26 mm2 Contact I O 18 AWG 0 8 mm2 14 AWG 2 1 mm2 a For all connection types the insulation voltage must be 300 V minimum Dielectric Str...

Страница 16: ...Ground 64S Pickup Range OFF 0 1 k 10 k primary Pickup Measurement Accuracy Steady State 10 of pickup 50 for pickup 2 k 15 pickup for 2 k pickup 10 k Time Delay Range 0 1 400 0 seconds Time Delay Accur...