SEL- 2664S Data Sheet

Schweitzer Engineering Laboratories, Inc.

4

Profile Report Monitoring

Profile report monitoring provides a periodic snapshot
(selectable rate of every 1, 5, 15, 30, or 60 minutes) of as
many as 17 selectable analog quantities from the
complete list of analog quantities the SEL-2664S
generates. Examples of analog quantities available
include the following:

Stator insulation resistance

Injected rms current

Neutral ground resistance

Third-harmonic neutral voltage

When used with the SEL-2664 Field Ground Module, the
relay can also record the field insulation resistance.

The SEL-2664S maintains profile information in a
nonvolatile buffer memory. The memory can hold data for
9800 time-stamped entries. 

Automation

Flexible Control Logic and Integration Features

The SEL-2664S has three independently operated serial
ports: one front and one rear EIA-232 serial port and one
rear fiber-optic serial port. Also, the relay supports dual
fiber Ethernet ports in the rear. The relay needs no special
communications software. You can use any system that
emulates a standard terminal system. Establish
communication by connecting computers, modems,

protocol converters, printers, an SEL real-time
automation controller (RTAC), SEL communications
processor, SEL computing platform, SCADA, and/or
RTUs for local or remote communication. Refer to

Table 2

 for a list of communications protocols available in

the SEL-2664S.

Neutral Currents (A sec)

Magnitude of neutral currents at the injected frequencies in secondary amperes

Stator Insulation (k

)

Resistance of the stator insulation to ground at the injected frequencies in kilohms, primary

a

Secondary and Primary reference the Neutral Grounding Transformer (NGT), not CTN.

b

Neutral current (A sec) is shown if CTN_LOC := SEC; otherwise, it is hidden.

Table 1

Metered Quantities

 (Sheet 2 of 2)

Quantities

Description 

Table 2

Communications Protocols

Type

Description

Simple ASCII

Plain language commands for human and simple machine communication. 
Use for metering, setting, self-test status, event reporting, and other functions.

Compressed ASCII

Comma-delimited ASCII data reports. 
Allows external devices to obtain relay data in an appropriate format for direct import into spreadsheets and 
database programs. Data are checksum protected.

Fast Meter and Fast 
Operate

Binary protocol for machine-to-machine communication. 
Quickly updates SEL communications processors, RTUs, and other substation devices with metering informa-
tion, relay elements, I/O status, time tags, and summary event reports. Data are checksum protected. Binary and 
ASCII protocols operate simultaneously over the same communications lines, so there is no loss of control, sta-
tus, or metering information while a technician transfers an event report.

Fast SER Protocol

Provides SER events to an automated data collection system.

Modbus

Serial or Ethernet-based Modbus with point remapping. 
Includes access to metering data, protection elements, contact I/O, targets, SER, relay summary event reports, 
and settings.

DNP3

Serial or Ethernet-based DNP3 protocols.

Provides default and mappable DNP3 objects that include access to metering data, protection elements, Relay 
Word bits, contact I/O, targets, SER, and relay summary event reports.

IEC 61850

Ethernet-based international standard for interoperability among intelligent devices in a substation.

 

Operates remote bits and I/O. Monitors Relay Word bits and analog quantities.

SNTP

Ethernet-based protocol that provides time synchronization of the relay.

Содержание SEL-2664S

Страница 1: ...ge elements Operator Controls Take advantage of multiple methods for accessing and using the operator interface of the relay The front and side panels have eight LEDs that indicate the ENABLED TRIP WA...

Страница 2: ...imple Network Time Protocol SNTP File Transfer Protocol FTP Telnet SEL ASCII SEL protocols including MIRRORED BITS communications Conformally Coated Overview Figure 1 Functional Diagram Operator Inter...

Страница 3: ...of the 64S elements described previ ously The combination of the two with their over lapping coverage provides 100 percent stator winding protection 100 percent of the time Neutral Ground Resistor Mo...

Страница 4: ...ry and Primary reference the Neutral Grounding Transformer NGT not CTN b Neutral current A sec is shown if CTN_LOC SEC otherwise it is hidden Table 1 Metered Quantities Sheet 2 of 2 Quantities Descrip...

Страница 5: ...ction or control schemes with eight general purpose SELOGIC control equa tion timers Each timer has independent time delay pickup and dropout settings Program each timer input with any element you nee...

Страница 6: ...ickSet in the following ways Develop settings offline with an intelligent settings editor that only allows valid settings Create SELOGIC control equations with a drag and drop text editor Configure pr...

Страница 7: ...under 26 V peak If a generator produces VN3 above this level even under normal load conditions the injection signal stops disabling the 64S elements However 59N1 59NRMS and 64F elements continue to pr...

Страница 8: ...for protection using redundant relays shown with neutral CTs on the secondary side of the neutral grounding transformer This application requires Relay 1 to set the Injection Source Mode setting MODE_...

Страница 9: ...for a typical example of the dc connections for 100 percent stator ground protection using the SEL 2664S Stator Ground Protection Relay stator to ground insulation resistance measurement and the SEL...

Страница 10: ...SEL 2664S Data Sheet Schweitzer Engineering Laboratories Inc 10 Relay Mounting and Dimensions Figure 15 SEL 2664S Wall Mount Dimensions Figure 16 SEL 2664S Connection Diagram for Wall Mount Option...

Страница 11: ...Engineering Laboratories Inc SEL 2664S Data Sheet 11 Figure 17 SEL 2664S Panel Mount Dimensions Figure 18 SEL 2664S Connection Diagram for Rack and Panel Mount Options Figure 19 SEL 2664S Rack Mount...

Страница 12: ...C Injection Source Connections Port 3 EIA 232 Serial Port Terminal C Neutral Current IN Connections Terminal B Power Supply 125 250 Vdc or 110 240 Vac Port 2 Fiber Optic EIA 232 Serial Port Terminal A...

Страница 13: ...40 Hz Maximum Open Terminal Voltage 26 V peak Protection Self protecting Power Supply Relay Start Up Time Approximately 5 10 seconds after power is applied until the ENABLED LED turns on High Voltage...

Страница 14: ...Telnet SNTP IEC 61850 MIRRORED BITS Operating Temperature IEC Performance Rating per IEC EN 60068 2 1 and 60068 2 2 40 to 85 C 40 to 185 F Not applicable to UL applications Operating Environment Insul...

Страница 15: ...mm2 14 AWG 2 1 mm2 Potential Voltage VN 16 AWG 1 3 mm2 10 AWG 5 26 mm2 Contact I O 18 AWG 0 8 mm2 14 AWG 2 1 mm2 a For all connection types the insulation voltage must be 300 V minimum Dielectric Str...

Страница 16: ...Ground 64S Pickup Range OFF 0 1 k 10 k primary Pickup Measurement Accuracy Steady State 10 of pickup 50 for pickup 2 k 15 pickup for 2 k pickup 10 k Time Delay Range 0 1 400 0 seconds Time Delay Accur...

Отзывы: