TB MRU3-1 12.00 E
9
5
Operations and settings
5.1
Display
Function
Display shows
Pressed pushbutton
Corresponding LED
Normal operation
SEG
Measured operating values
Actual measured values
<SELECT/RESET> one time
for each value
L1, L2, L3,
Transformer ratio of the CT’s
(SEK) 1.01 – 6500=prim
<SELECT/RESET><+><->
L1, L2, L3
Setting values:
star/delta connection
Y/DELT
<SELECT/RESET><+><->
∆
/Y
Parameter switch/ext. triggering
for the fault recorder
SET1, SET2, B_S2, R_S2,
R_S2, B_FR, R_FR, S2_FR
<SELECT/RESET><+><->
P2
Switch-over LED flash
No LED flash
FLSH
NOFL
<SELECT/RESET>
<+><->
undervoltage (low set)
tripping delay of low set element
setting value in volt
setting value in seconds
<SELECT/RESET><+><->
one time for each value
U<
t
U<
undervoltage (high set)
tripping delay of high set element
setting value in volt
setting value in seconds
<SELECT/RESET><+><->
one time for each value
U<<
t
U<<
overvoltage (low set)
tripping delay of low set element
setting value in volt
setting value in seconds
<SELECT/RESET><+><->
one time for each value
U>
t
U>
overvoltage (high set)
tripping delay of high set element
setting value in volt
setting value in seconds
<SELECT/RESET><+><->
one time for each value
U>>
t
U>>
rated frequency
setting value in Hz
<SELECT/RESET><+><->
f
N
U</U> 1-phase/3-phase
U<>1/U<>3
<SELECT/RESET><+><->
1/3
Blocking function
EXIT
<+> until max. setting value
<-> until min. setting value
LED of blocked
parameter
Slave address of serial interface
1 - 32
<SELECT/RESET><+><->
RS
Baud-Rate
1)
1200-9600
<SELECT/RESET> <+><->
RS
Parity-Check
1)
even odd no
<SELECT/RESET> <+><->
RS
Recorded fault data:
star--connection: U1, U2, U3
tripping values in Volt
<SELECT/RESET><+><->
one time for each phase
L1, L2, L3, U<, U<<,
U>, U>>
delta-connection: U12, U23, U31
tripping values in Volt
<SELECT/RESET><+><->
one time for each phase
L1, L2, L3, U<, U<<,
U>, U>>
Save parameter?
SAV?
<ENTER>
Save parameter!
SAV!
<ENTER> for about 3 s
Delete fault memory
wait
<-> <SELECT/RESET>
Enquiry fault memory
FLT1; FLT2.....
<-><+>
L1, L2, L3
U<, U<<, U>, U>>
Trigger signal for the fault recorder
TEST, P_UP, A_PI, TRIP
<SELECT/RESET> <+><->
FR
Number of fault occurences
S = 2, S = 4, S = 8
<SELECT/RESET> <+><->
FR
Display of date and time
Y = 99, M = 10,
D = 1,
h = 12, m = 2, s = 12
<SELECT/RESET> <+><->
!
Software version
First part (e.g. D02-)
Sec. part (e.g. 6.01)
<TRIP>
one time for each part
Manual trip
TRI?
<TRIP>
three times
Inquire password
PSW?
<SELECT/RESET>/
<+>/<->/<ENTER>
Relay tripped
TRIP
<TRIP> or fault tripping
Secret password input
XXXX
<SELECT/RESET>/
<+>/<->/<ENTER>
System reset
SEG
<SELECT/RESET>
for about 3 s
1)
only Modbus
Table 5.1: Possible indication messages on the display