SEQUENCER CONTROLLER
WITH OR WITHOUT
DIFFERENTIAL PRESSURE SWITCH
Technical notice
FI 72.0297.1016E
Page 3
CHARACTERISTICS
- Mains Voltage (rated voltage)
115V or 230V
+ 10 % 50-60 Hz
- Power consumption (rated current)
Output power: 25VA / 25W
If S.V. voltage
24VAC or 24VDC: 230Vac-150mA / 115Vac-300mA
48VAC or 48VDC: 230Vac-150mA / 115Vac-300mA
If S.V. voltage = sector voltage:
230Vac-35mA / 115Vac-70mA + S.V. consumption (2,5A Maxi)
Output power: 45VA / 40W
If S.V. voltage
24VAC or 24VDC: 230Vac-250mA / 115Vac-400mA
If S.V. voltage = sector voltage:
230Vac-35mA / 115Vac-70mA + S.V. consumption (2,5A Maxi)
- Solenoïd valves voltage:
Same mains voltage (2.5A maxi current)
or 24VAC integrated (25VA max) or 24VDC integrated (25W max)
or 48VAC integrated (25VA max) or 48VDC integrated (25W max)
or 24VAC integrated (45VA max) or 24VDC integrated (40W max)
- Inputs characteristics:
Voltage: 24VDC supplied by the device
Loading c/- 10mA
- Relay contacts characteristics:
Dry contacts 1A 250V AC1
(to be protected by the user)
- Running temperature:
-20° to 60°C
- Storage temperature:
-20° to 70° C
- Device protection:
By fuses size 5x20: F1=F500mA / F2=F1A / F7, F8=F2.5A
Output power: 25VA / 25W
F3, F4=T500mA (supply in 115V) or T250mA (supply in 230V)
F5, F6=T1A (S.V voltage=48V) or T1.6A (S.V voltage=24V)
Output power: 45VA / 40W
F3, F4=T630mA (supply in 115V) or T315mA (supply in 230V)
F5, F6=F2.5A (S.V voltage=24V)
- Case:
ABS IP65 IK07 material
SEQUENCER CONTROLLER:
- Maxi outputs number
36
- Activation time of an output (T1)
from 3/100
th
to 255/100
th
of a second
- Idle time between two outputs T2
(T2A if it’s equipped with the DP)
from 1 to 255 seconds
- Rest time between two cycles (T3)
from 0 to 255 minutes
- Controlled cleaning time (T4)
from 0 to 255 hours
- Number of cycles if fan stop
0 to 255 cycles
- Number of cycles manual running
0 to 255 cycles