background image

14 

 |   

INTERNATIONAL

ILL1014-I

TEST OPERATION

Check that the green light on the electronics module is on and 

double flashing every 2 seconds. This indicates that power is 

connected to the electronics module. 

Important!

 Ensure the flexible splash protection cover is put 

back in place.

Fault Code 01 (1 Red Flash) = Communication Failure.

• 

Ensure wall control cable is fitted correctly.

•  Check the wall control cable is in good condition.

Fault Code 02 (2 Red Flashes) = Failure to detect water at 

probes within 8 minutes.

• 

Ensure water pressure is sufficient to fill and maintain the tank 

to specified level within 8 minutes. 

•  In areas of hard or polluted water, blockage of the strainer/

filter in the water inlet solenoid valve may restrict water flow. 

•  Water level set too low. The water level should be set to 5mm 

(3/16”) below the float valve base. 

•  Ensure probe plug is properly connected.

•  Plug connections at electronic module are upside down or 

misaligned. 

•  Water too pure for the probes to sense water is present.

•  Pressure build up in pipes can lock up the solenoid valve 

when a non-return isolation valve is used in the water supply 

line. It is recommended to use a ball valve, i.e. NOT a non-

return type of shut off valve.

•  Check drain valve is closing and not cycling due to debris 

being caught under drain valve washer.

Fault Code 04 (4 Red Flashes) = Failure to clear probes 

during drain within 4 minutes.

•  Check the drain valve opens and water drains from the tank, 

with nothing obstructing the outflow of water. (e.g. drain hose 

kinked)

•  Excessive drain hose lengths or bends cause air locking and 

won’t allow water to drain.

•  Build up of foreign material in drain hose not allowing water to 

drain away correctly.

• 

Screws used to fix drain hoses to drain adaptors restricting 

water from draining from tank.

•  Drain valve has failed to open when drain was initiated.

•  Inlet water solenoid not shutting off water when the drain is 

open.

SETTING THE WATER LEVEL 

cont

If the level is too high rotate the float clockwise. Drain some water 

from the tank and allow it to refill to the new set point.  If too low 

rotate the float in an anti-clockwise direction. The correct water 

level is approximately 5mm below the surface of the tank the float 

valve is mounted on. It is advisable to check the water level again 

after the float valve washer has “bedded in”.

FAULT CODES INDICATED BY LED’s ON 

THE COOLER ELECTRONICS MODULE

Once the water level is correct, isolate the control box and 

connect the pump plug.

ILL998-D

COMMISSIONING THE COOLER

FAULT CODES INDICATED BY LED’s ON 

THE COOLER ELECTRONICS MODULE 

cont

Fault Code 04 (4 Red Flashes) = Failure to clear probes 

during drain within 4 minutes - cont.

• 

Water will only flow one way through the inlet water solenoid 

valve. Therefore, it must be installed correctly. Directional 

arrow must be pointing towards the float valve assembly. If 

not, water will not shut off. (Directional arrow can be found on 

the bottom of the solenoid valve body). 

•  Debris interfering with water sensor probes. 

•  Probes not clipped onto mounting brackets correctly.

•  Check cooler is level and water drains quickly.

Fault Code 07 (7 Red Flashes) = Incorrect supply frequency 

(Hz). (TBQ, TBS & CPQ coolers only)

This fault will only be seen when the mains power supply 

frequency deviates from normal frequency by more than 8%. 

Mains power supply frequency should be 50 or 60Hz. 
•  Petrol generators are the most likely cause of this type of 

fault. This typically will not occur on mains power supplies.

EXTRA NOTES FOR LCQI, TBQI & TBSI 

COOLERS ONLY

Fault Code 07 (7 Red Flashes) = Motor Error. 

(MagIQtouch Controller Only)

ILL2120-A

LCQ, LCS, TBQ, TBS, 

BMQ & CPQ coolers

LCQI, TBQI & TBSI coolers

Note!

 If on initial start up the word “Service” appears on the 

controller and by pushing the button nothing changes on the 

display, then you will need to establish communication between 

the wall control and the electronic controller. 
Simply push and hold the button for approx. 10 seconds or until 

the word “Service” disappears. 

If by pushing the button a number appears refer to the fault 

codes.

Содержание BMQ

Страница 1: ...INSTALLATION MANUAL LCQ LCS LCQI BMQ CPQ TBS TBQI TBSI TBQ Evaporative Cooler Original English Instructions Original English Instructions ...

Страница 2: ...AN ASSEMBLY 11 ELECTRICAL CONNECTION 11 CONNECTING THE WATER PUMP 12 CONNECTING THE MAGIQTOUCH MAGIQCOOL CONTROLLER 12 MAGIQTOUCH CONTROLLER DISPLAY INFORMATION 13 CHANGING THE WATER MANAGEMENT METHOD FOR THE MAGIQCOOL CONTROL 13 CHANGING THE SALINITY CONTROL METHOD FOR THE MAGIQCOOL CONTROL 13 SETTING THE WATER LEVEL 13 FAULT CODES INDICATED BY LED s ON THE COOLER ELECTRONICS MODULE 14 COMMISSION...

Страница 3: ...s it is just is a matter of looking at the job to be done and considering what action s are necessary so the person doing the job does not injure themselves This should be considered in terms of What are the chances of an incident happening What could the possible consequence be What can you do to reduce or better still completely eliminate the risk Some points to consider What is the best and saf...

Страница 4: ...cation Consider regulations Discuss with customer Step 8 CHECK AutoWinterseal Check operation of the AutoWinterseal Ensure AutoWinterseal moves freely Step 15 INSTALL DRAIN VALVE Never drain waste water directly onto the roof Be sure to use supplied O Rings and fittings Step 3 REMOVE VENTURI Press the clip or remove the screws on both sides of the venturi to release Step 9 CONVEY COOLER TO ROOF Pa...

Страница 5: ...sition Step 5 PREPARE THE DROPPER Cut hole fit the grommet in the dropper for power and control cables Step 11 CABLE INSTALLATION Run the power and control cable down the conduit and out through the grommet Step 17 INSTALL VENTURI FAN Ensure the venturi is fully located into the tank and the motor lead is not caught or pinched Step 6 MOUNT DROPPER Position level and secure the dropper Flash the dr...

Страница 6: ...ust be mounted at least 3m 10 preferably 5m 17 away from any TV antenna or antenna cables Make sure the cooler is not between the antenna and the transmission tower that is providing the television signal to the home Allow adequate access to and around the cooler for maintenance Provision must be made for access to electricity water supplies and drains Note Do you need to discuss the installation ...

Страница 7: ...dropper is suitable and is secured adequately for wind conditions at the site Additional restraints may be required if the cooler is more than 200mm 8 higher than the roof timbers or design wind velocity at the site exceeds 43m s 141fps In exposed or very high wind areas use 16 screws minimum shank diameter 5 2mm 7 32 to secure the dropper In areas subject to hurricanes windstorms or where the coo...

Страница 8: ...tach ropes or slings through the central tank hole Do not slide the cooler lift and carry it Do not drop the cooler Always handle the cooler with care AutoWinterseal CONVEYING THE COOLER TO THE ROOF Caution Do not take risks when raising the cooler to the roof for installation Use safety equipment appropriate procedures and always have assistance It is recommended that at least 2 people move the c...

Страница 9: ...lot in the transition control cable first and then seal the hole with the plug provided Important Test the AutoWinterseal operation and ensure that the cables in the dropper do not interfere with the operation of the assembly ILL1288 C ILL1181 A CABLE INSTALLATION cont CABLE INSTALLATION For Rest of the World Pass the taped end of the wall control cable through the conduit adaptor factory fitted i...

Страница 10: ... required Water Connection BSP Min Water Pressure 100kPa 15psi Max Water Pressure 800kPa 115psi Min Water Flow 8 liters min 2 1 gallons min Max Water Temperature 40 C 104 F Important If the water pressure exceeds maximum specification then a pressure reducing valve is required and must be supplied and fitted by the installer A permanent water supply is required to be connected to the cooler The wa...

Страница 11: ...d valve then push the other end through the hole in the transition as shown Pull the cable through from inside the cooler and route the cable as shown This will be connected later INSTALLING THE INLET SOLENOID INSTALLING THE FLOAT VALVE Assemble the float valve to the cooler as shown Ensure all washers and O rings are in place No thread tape is required Do not over tighten the plastic fittings Mak...

Страница 12: ...EED FUNNEL Assemble the bleed funnel as shown Make sure the bleed funnel is correctly oriented and that the o rings are fitted before placing it into the hole Screw the nut up tightly by hand underneath the cooler Make sure that you use the correct drain adaptor Drain water from the bleed funnel must be carried away to a suitable discharge point on the building or property in accordance with local...

Страница 13: ...e sits Snare the lead into one of the brackets at the top of the opening E Ensure the bottom of the lead is aligned with the bracket inside the tank Failure to do this may result in the cable being caught between the outside of the bracket and the venturi A If fitted route the motor tether through bracket at A and wedge it between the venturi and the tank at edge B ELECTRICAL CONNECTION Connect th...

Страница 14: ...trol cable Longer cable lengths are available from Seeley Important The maximum cable length allowed from the MagIQtouch Controller to the first cooler is 25m 82 For any additional coolers added into the system with a link module the maximum allowed length is 40m 131 Therefore failure of the product or components to operate correctly due to modification to supplied cables or the use of non approve...

Страница 15: ...down for at least 3 seconds and then press while still pressing The setting A1 will be displayed release both buttons and then press A number will now be displayed Press or until the number displayed corresponds to the desired setting 0 Salinity Control 1 Timed Drain every 65 mins Press to complete the adjustment Exit the programming mode by pressing To enter Parameter mode the following process m...

Страница 16: ...G THE WATER LEVEL cont If the level is too high rotate the float clockwise Drain some water from the tank and allow it to refill to the new set point If too low rotate the float in an anti clockwise direction The correct water level is approximately 5mm below the surface of the tank the float valve is mounted on It is advisable to check the water level again after the float valve washer has bedded...

Страница 17: ... to the cooler was made NO EXTERNAL LEAKS The water is connected with no leaks at fittings NO INTERNAL LEAKS Check the internal water hose is securely fitted to water distribution spreader on the lid and to the pump SECURE Water pipes are correctly saddled as per plumbing regulations OWNER INSTRUCTIONS The owner has been instructed on how to isolate the water to the system in case of emergency DRA...

Страница 18: ...TINGS COMMISSIONING COMPLETION CHECKLIST cont POWER REGULATIONS The power supply adheres to all local and national regulations and is wired back to the distribution board on its own separate circuit CHECK CABLES Cables have been correctly connected to the control boxes Power supply Motor cable s Control cable Drain valve Solenoid cable Pump cable Probe cable OWNER INSTRUCTIONS The owner has been i...

Страница 19: ...fault condition via the tri colour LED on cooler electronics module Rectify fault as indicated and restart the cooler Controller failure Replace controller Pump runs but no water circulation or Pump runs but pads lack water Insufficient water in tank Adjust float level Water hoses blocked Check and clean out blockage Pump strainer blocked Clean pump strainer Insufficient water supply pressure Chec...

Страница 20: ... Please contact your local distributor seeleyinternational com MANUFACTURED BY SEELEY INTERNATIONAL PTY LTD 112 O SULLIVAN BEACH RD LONSDALE SA 5160 AUSTRALIA IMPORTED BY SEELEY INTERNATIONAL EUROPE LTD UNIT 11 BYRON BUSINESS CENTRE DUKE STREET HUCKNALL NOTTINGHAM NG15 7HP UNITED KINGDOM SEELEY INTERNATIONAL AMERICAS LTD 1202 NORTH 54TH AVENUE BUILDING 2 SUITE 117 PHOENIX ARIZONA 85043 USA SEELEY ...

Отзывы: