LCQ / LCS / LCQI / BMQ / CPQ / TBQ / TBS / TBQI / TBSI EVAPORATIVE COOLER INSTALLATION MANUAL
|
13
ILL1714-A
ILL1615-A
Turn on the mains water supply to the cooler.
Turn the cooler on at the controller, in “COOL” mode.
Adjust set temperature slider / fan speed buttons to be close to
current room temperature so that fan speed remains low.
Allow the tank (reservoir) to fill with water. The float valve will
eventually stop the water from entering the cooler. Wait for this
to happen and check the water level.
Cooler operating information is available from the ‘Service
Operating Screen’ under the COOLER tab of the SETTINGS
menu.
Isolate power to the cooler electronics and disconnect the
pump, making sure the plug is kept away from any water. Turn
the power back on.
ILL1663-A
ILL997-C
ILL1664-A
Diagnosis and cooler operating information can also be viewed
from the MagIQtouch Controller. Faults are displayed on the
screen as they occur.
SETTING THE WATER LEVEL
CHANGING THE WATER MANAGEMENT
METHOD FOR THE MAGIQCOOL CONTROL
ILL2117-A
ILL2118-A
MAGIQTOUCH CONTROLLER
®
DISPLAY
INFORMATION
CHANGING THE SALINITY CONTROL
METHOD FOR THE MAGIQCOOL CONTROL
For models where water management probes and drain valve
are fitted, the drain frequency is typically managed by salinity
control. There should be no need for adjustment. However if
you do wish to change from salinity control to regular operation
of the drain valve every 65 mins, follow these programming
steps.
While the thermostat is OFF, hold down
for at least 3
seconds and then press
while still pressing
.
The setting “A1” will be displayed, release both buttons and
then press
.
A number will now be displayed. Press
or
until the
number displayed corresponds to the desired setting;
0 = Salinity Control
1 = Timed Drain every 65 mins.
Press
to complete the adjustment. Exit the programming
mode by pressing
.
To enter Parameter mode, the following process must be
carried out within 4 minutes of power being applied to the
cooler. If unsure of time since the last power “ON”, remove
power to the cooler (Isolator Switch or Circuit Breaker) for a
minimum of 6 seconds so the mode can be entered.
1. While wall control is OFF, push and hold
“
” and “
” button for minimum three (3) seconds.
2. When parameter mode has been entered, screen will display
“A1” - (Water Salinity Control Method) and “Param”.
3. To view parameter number set in wall control press
“
” momentarily. Figure “A#” on screen will change to
number set, and “Param” will change to “value”.
4.
To alter the “value” of selected parameter press “
” or
“
”. Numbers will change to show different values the
parameter can be set to.
Water Manager = 0
Timed Drain (CPQ & BMQ Upgrade Kits) = 1
Non-Drain Valve salinity control (bleed etc) = 2
5. To store the value, press “
”. Screen will go blank
momentarily as wall control stores parameter change, and
returns screen to “A#” and “Param”.
6. To exit parameter mode or escape from an alteration without
storing a change press
“
” button instead of “
” button. Remember, once
step 5 has been carried out, new parameter change is
permanent until again altered.
7. If no buttons are pushed on wall control, after 3 minutes
screen will reset to “OFF” state. Procedure to enter parameter
mode must be re-initiated.