8
|
INTERNATIONAL
Installation of the cooler must conform to local electrical rules,
regulations and standards.
Important!
It is a requirement of Seeley International that all
coolers be connected to a dedicated circuit to the distribution
board, with a separate circuit breaker and incorporate a separate
isolation switch in accordance with the local wiring rules.
The following specifications for the cooler electrical supply are
required:
220V or 230V or 240V or 220-240V / 50Hz or 60Hz Single
Phase (see nameplate for exact data for the cooler)
For LCQ, LCS, TBQ, TBS, CPQ, BMQ models:
The electronics module is fitted with a 12A re-settable circuit
breaker. To reset the circuit breaker turn off the isolation switch,
remove the electronics module and push the manual reset
toggle switch located underneath the electronics module.
For LCQI, TBQI, TBSI models:
The electronics module is fitted with a 10A anti-surge fuse in
place of the 12A circuit breaker.
WARNING!
If the supply cord is damaged, it must be replaced
by the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
Installation of the cooler water supply must conform to
local plumbing rules, regulations and standards.
The following specifications for the cooler water
supply are required:
Water Connection
½
”
BSP
Min Water Pressure
100kPa (15psi)
Max Water Pressure
800kPa (115psi)
Min Water Flow
8 liters/min (2.1 gallons/min)
Max Water Temperature
40°C (104°F)
Important!
If the water pressure exceeds maximum
specification then a pressure reducing valve is required and
must be supplied and fitted by the installer.
A permanent water supply is required to be connected to the
cooler. The water connection point is located on the underside of
the cooler.
You must install a manual 1/4 turn ball type shut off valve (do not
use a stop cock) in the water supply line adjacent to the cooler,
subject to local plumbing regulations. This allows the water
supply to be isolated whenever work needs to be done on the
cooler.
The water connection is a 1/2” BSP compression fitting or a 1/2”
BSP to 1/4” compression fitting. This can fit directly onto the
water pipe or be screwed directly onto the manual water shut-
off valve.
Always ensure that the water pipe connection does not place
sideways strain onto the float valve.
Important!
In areas subject to freezing, the water supply line
to the cooler requires a drain down facility at the lowest point in
the water supply pipe.
Important!
Flush the water pipe to remove any swarf before
final fitting. Swarf can lodge in the solenoid and float valve,
preventing them from functioning correctly.
ELECTRICAL REQUIREMENTS
WATER REQUIREMENTS
ILL1898-A
FIELD WIRING DIAGRAM
For models that require fixed wiring use the following.