13
TQ3, TQ4, TQ5, TQM5, TQM6, TQS3, TQS4, TQS5, TQS6
FLUE SYSTEM & CONDENSATE DRAIN TQ5, TQM6, TQS5, TQS6
Flue system
Braemar TQ5, TQM6, TQS5, TQS6 heaters must be flued using 100mm DWV plastic pipe and components complying with AS1260.
The flue terminal on the side of the heater is designed to accept either the male end of a 100mm DWV M-F elbow, or 100mm DWV pipe.
Connections
The connection to the heater, and all other joins in the flue and condensate drain system must be sealed to prevent leakage of
condensate.
USE SILICONE SEALENT OR PVC SOLVENT CEMENT AND PRIMER FOR ALL CONNECTIONS.
Flue treminal
The flue system must be terminated to outside with a 100mm DWV vent cowl as shown in the installation diagrams.
This is supplied in both internal and external installation accessories kits.
Maximum flue length
Maximum vertical rise : 5 metres,
Maximum total flue length 12 metres,
Maximum number of bends 4 x 90° (2 x 45° bends = 1 x 90°).
Condensate drain
Use either 15mm rigid PVC pressure pipe or 20mm rigid PVC electrical conduit.
Do not allow condensate to be discharged over electrical connections, earth stakes, concrete paths, copper pipes or metallic roofs.
Do not discharge directly into guttering.
Condensate can be discharged into a vent pipe via a tundish and self-sealing device, or into a vertical section of a downpipe via a tundish.
Condensate drain must run down hill from connection point on heater to point of discharge - do not allow any part to run up-hill.
Condensate drain must be well supported.
Do not allow condensate to be discharged into any potable water system or potable water system collection point.
Fit insulation (eg, Armaflex)over full length of condensate drain line in sub-zero climates.
INSTALLING THE DUCT THERMISTOR TQ4, TQ5, TQM5, TQM6, TQS3, TQS4, TQS5, TQS6
Thermistor location is CRITICAL to the correct operation of the heater
The outlet air temperature thermistor must be installed in the outlet air duct approximately 3 metres of duct length from the
heater outlet.
On systems with more than 1 outlet duct from the heater the thermistor must be located in the duct that always has air flow.
Thermistor must be installed in a duct that always has airflow, and never in a duct that can be turned off in a zoned system.
To Install the Thermistor
Drill a 12mm hole in either the BTO or duct ensuring 3 metres of duct length from the heater outlet.
Feed the thermistor and bracket through the grommet in the side of the heater.
Insert the bracket into the hole in either the BTO or duct and screw of securely tape into place.
Seal the hole.
Coil and secure any excess thermistor cable outside the heater.
3 m
3 m
Heated air
Heated air
Return air
duct
Return air
duct
Duct or BTO
Screw
Thermistor
bracket
Thermistor
12mm hole
Tape
Thermistor must be
installed in a duct that
always has airflow