Flue connection - Non modulating heaters
Flue connection - modulating heaters
UNDER-FLOOR INSTALLATION
There is to be a minimum clearance of 200mm between the lowest part of the floor structure and any part of the heater.
The heater is to be located within 2m of the access opening, or there is to be a minimum clearance of 1.2m between the lowest part of
the floor structure. and the ground level, maintained from the access opening to the appliance.
The heater must be mounted on a level concrete base of at least 50mm thick as per the slab dimensions or suspended above the ground.
Fixed artificial lighting must be provided at the heater, with the switch located adjacent to the access opening.
FLOOR
concrete base
DUCT
HEATER
FLUE
External Wall
200mm minimum
for servicing
Flue to terminate
outside building
External flue
terminal (Die cast)
Pre drill a 5mm hole in
the powder coated die
cast flue terminal
Attach flue terminal to
flue, fixing in place with
screw.
Light switch must
be adjacent to
access opening
External flue
cover kit available.
P/No 079073.
Terminate condensate
drain in a suitable location
Fix flue pipe in
place with screw
Remove & discard
transit plugs
Vent cowl, condensate drain tee
assembly, flue drain elbow and flue
drain hose are supplied in TQ5
internal installation accessories kit.
P/No 075525
Condensate drain tee
assembly
Flue drain elbow
Vent cowl
Flue drain hose
SEAL CONNECTIONS: Seal flue and condensate drain
connections using
silicone sealant or
PVC primer and
solvent cement.
INSULATE DRAIN LINE: Fit insulation (eg, Armaflex)
over full length of condensate drain line in sub-zero
climates.
FLOOR
concrete base
DUCT
HEATER
FLUE
External Wall
200mm minimum
for servicing
Flue to terminate
outside building
Light switch must
be adjacent to
access opening
External flue
cover kit available.
P/No 079073.
Terminate condensate
drain in a suitable location
Fix flue pipe in
place with screw
Remove & discard
transit plugs
Flue terminal, condensate drain tee
assembly, flue drain elbow and flue
drain hose are supplied in
installation accessories kits.
P/No 075563
Condensate drain tee
assembly
Flue drain elbow
Flue drain hose
SEAL CONNECTIONS: Seal flue and condensate drain
connections using silicone sealant or PVC primer and
solvent cement.
INSULATE DRAIN LINE: Fit insulation (eg, Armaflex)
over full length of condensate drain line in sub-zero
climates.
With timber
side wall
Use side wall flue
heat shield kit
P/No 077420.
With timber
side wall
Use side wall flue
heat shield kit
P/No 077420.
External flue
terminal
(Metal Powder
coated)
Rise:
Minimum 10mm/m
for horizontal runs
Heaters
TQ516
TQ523
TQ5X23
TQ532
TQ5X32
TQM618
TQM623
TQM6X23
TQM632
TQM6X32
TQS523
TQS5X23
TQS623
TQS6X23
Heaters
Heaters
TQ315
TQ320
TQ3X20
TQ325
TQ3X25
TQ330
TQ3X30
TQ415
TQ420
TQ4X20
TQ425
TQ4X25
TQ430
TQ4X30
TQ435
TQS320
TQS3X20
Heaters
TQM516
TQM520
TQM5X20
TQM530
TQM5X30
TQS420
TQS4X20
Rise:
Minimum 10mm/m
for horizontal runs