Commissioning
38 / 41
Mounting and Installation, Technical Description, T 811 065 en
6.4
Possible displays & fault patterns
6.5
Simple troubleshooting
After a successful commissioning, no faults appear on the control panel. As soon as something is not OK, fault patterns may
occur.
6.5.1
General
Faults are indicated on the indication and control map of the SecuriFire both optically (collective malfunction indication) and
audibly (warning sound). In addition, the type and number of faults are displayed in the fault list in the display.
You can select the fault list via the MIC and browse in the display of the indication and control map.
If you want to view additional information about a particular fault, you must select the concerned message with the
Securi-
Wheel
.
Pressing the
More info
button shows the information in the display. With the
More info
button you can select either SITE
INFO or INFO in plain text.
6.5.2
Contaminated detector
This is displayed by the
Call service
pictogram and in a contamination list on the indication and control map of the SecuriFire.
The following procedure is recommended for contaminated detectors:
•
Press the
Lists
button, select the WARNINGS entry, press the
Enter
key.
•
The detector contamination list displays and can be browsed with the
SecuriWheel
.
•
Contaminated detectors must be replaced by new or cleaned detectors.
•
In user level 3 (password entry required) the detector contaminations can be reset.
6.5.3
Possible causes of faults
System
Defect on the B7-CPB11 main control unit, on the B7-MIC11 indication and control map, or
on the integrated power supply unit etc. (detailed information can be displayed on the Ser-
vice monitor).
Detectors / detection zones
Short-circuit, wire breakage, lacking end base (monologue technology), programming (DZ)
do not match jumper setting (input) etc.
Inputs
Short-circuit, wire breakage, programming (input) do not match jumper setting (DZ) etc.
Outputs
Short-circuit, wire breakage, wrong load size or load range set etc.
Addressable loop
Logical fault (INIT FAULT, SYSTEM FAULT, ADDRESS FAULT), physical fault (wire break-
age, short-circuit, earthing).