Interfaces & connections
14 / 41
Mounting and Installation, Technical Description, T 811 065 en
3 Interfaces & connections
3.1
B7-CPB11 main control unit
The B7-CPB11 (
C
ontroller and
P
ower Supply
B
oard) main control unit is a component of every SecuriFire 500 control panel
and includes all interfaces for connecting peripherals, monitored inputs and outputs, service PC and the integrated power
supply unit. The mounting main indication and control map is connected to the main control unit using a ribbon cable.
Fig. 6 B7-CPB11 main control unit
System states are indicated by LEDs (V 50). All programming and configuration procedures are performed via the LAN inter-
face (X13) by means of the service PC and SecuriFire Studio.
3.1.1
Interfaces
X1
Mains connection 230 V / 110 V
X2
Control panel interface to the B7-MIC11
X5
Interface of the relay contacts
X6
Interface for EPI bus (extended bus)
X10
Interface for monitored inputs and outputs
X11
Output voltage for external consumers
X12
Interface for 1 addressable loop or 2 stub lines
(SecuriLine eXtended)
X13
Ethernet 100BASE-TX service interface for loading
program and planning data and for system diagnos-
tics
X14
Battery connection
T2
Button for control panel reset
V50
State LEDs for master processor
LED dark
fault
LED lit
startup
LED flashing
normal operation
T1
On/Off switch (power)
3.1.2
Technical data
Quiescent power consumption:
62.9 mA (battery current)
Supply voltage:
Battery voltage VL; VP +22 V .. 30 V
Logic voltage VCC +3.3V ± 5%
Rel. air humidity:
5% to 95%, without condensation
Ambient temperature:
-5° to +50°C
3.1.3
Compatibility notice
The B7-CPB11 main control unit as of version 20-1151100-01-01 is supported as of SecuriFire Studio Rel. 1.2.0.