ENFORCER Access Control Keypad with Proximity Card Reader
SECO-LARM U.S.A., Inc.
Direct Access to Programming (DAP):
Direct Access to Programming (DAP) is used to enter programming mode if the master code is
forgotten. DAP will not change the programming of the
SK-1131-SPQ
in any way.
To Use DAP:
1.
Disconnect the keypad’s power.
2. Wait one minute to ensure that the keypad’s power is fully discharged.
3. Reconnect the power. The keypad will beep repeatedly for one minute.
4. While the keypad is beeping, press the egress button once to stop the beeping.
NOTE
:
If no egress button is installed then use a small jumper wire to momentarily connect the
egress input and common ground terminals.
5.
Enter the DAP code:
2828 **
6.
The center green LED will now turn ON, indicating that the keypad is ready for a new master
code to be programmed.
NOTE
:
•
See “Programming the Master Code” on page 13 for how to program a new master code.
•
Direct Access to Programming (DAP) will not reset the keypad’s programming. It will only enter
programming mode in order to program a new master code.
•
For complete system reset, see “System Restore” on page 13.