Commissioning the logger
25
5.3
Switching the logger On/Off
The logger is switched on by the help of a magnetic switch.
NOTE
Before switching the logger on, all connected devices have to be
disconnected (unplug connectors) because the internal relays of the logger
are initiated during the switch-on process. Thus, connected devices could be
turned on and off unexpectedly and unintentionally.
Move the supplied magnet in front of the contact area
. After the magnet switch has
been activated, the
I/O
control lamp
is lit green for a moment and starts flashing
blue after the logger has been started up. The device is now in energy saving mode.
Whenever a radio or GSM connection is established and whenever a data transfer takes
place, the logger automatically switches to data transfer mode.
In order to switch the logger off, the magnet must be held in front of the contact area
for a few seconds while the
I/O
control lamp
is lit orange. As soon as the lamp
switches to red, the magnet has to be taken away from the contact area. Afterwards, the
logger switches off and the lamp goes out. Make sure to take the magnet away
immediately after the lamp switches to red. Otherwise, the logger reboots right after it
has been switched off.
Switching the device off has no effect on the measurement data stored. The
measurement data remain in the logger’s memory up to the time at which the device
receives new configuration data.
After being switched off and on again, the logger’s latest configuration still is
stored and can be retrieved, but it is no longer valid. The logger does not resume
measuring.
Furthermore, after being switched off and on again, the logger’s system time is
no longer current.
Therefore, the logger needs to be programmed anew after every restart.
5.4
Programming the logger
Prior to its on-site installation, the logger must be properly configured using the supplied
SebaDataView-3 software. In doing so, the logger has to be provided with the channel
allocation, the alarm conditions and the wireless connection parameters among other
things.
Please refer to the according chapter in order to get a detailed description of how to
configure the logger (see page 51).
Содержание Sebalog D-3
Страница 2: ...Consultation with SebaKMT 2...
Страница 8: ...Terms of Warranty 8...
Страница 26: ...Commissioning the logger 26...
Страница 34: ...Connecting the logger and installing it on site 34...
Страница 70: ...Programming the logger using the SebaDataView 3 software 70...
Страница 78: ...Retrieving and evaluating data 78...
Страница 88: ...Changing the battery 88...