ELECTRICAL

Figure 10 – 115/230 volt motor wiring
connections. 

Dual voltage motors come factory wired for 230 volt
operation. Inset shows 115 Volt conversion.

Do not alter wiring on single voltage motors. 

Match motor voltage to power supply voltage.

Risk of serious or fatal
electrical shock.

Connect motor ground wire
before connecting power
supply wires. 

Do not ground to a gas sup-
ply line.

Turn off power before work-
ing on pump or motor.

Match motor voltage and power supply voltage. 

Supply

voltage must be within ±10% of motor nameplate voltage.
Incorrect voltage can cause fire or seriously damage motor
and voids warranty. If in doubt, consult a licensed electri-
cian.

Use wire size specified in wiring chart.

If possible, con-

nect pump to a separate branch circuit with no other appli-
ances on it.
1. Install, ground, wire and maintain pump in accordance

with your local electrical code and all other codes/ordi-
nances that apply. Consult your local building inspector
for code information.

2. Connect ground wire first as shown at left. Ground wire

must be a solid copper wire at least as large as power sup-
ply wires.
• Connect ground wire to grounded lead in service panel,

metal underground water pipe, well casing at least 10’
(3M) long, or to ground electrode provided by power
company.

3. Connect power supply wires as shown at left.

6

A

B

L2

L1

A

B

L2

L1

To convert dual-voltage motors 
from 230 to 115 Volts: 
Move white wire w/black 
tracer from B to A.

Move black wire 
from A to L1.

NOTICE:  2 HP motors 
are 230 Volt only; 
do not connect 
to 115 volt power.

A

B

L2

L1

A

B

L2

L1

Clamp
power 
cable
to prevent
strain on
terminal
screws.

White w/
Black Tracer

Black

Motor Ground
Screw

Connect ground wire 
to motor ground screw 
as shown.

Connect power supply wires 
to the terminal board 
as shown.

Ground
Wire

Black

White

893 0494

WIRING CHART

Recommended Wire and Fuse Sizes

DISTANCE IN FEET FROM MOTOR TO METER

Branch

0’

51’

101’

201’

301’

401’

Max.

Fuse*

Min.

TO

TO

TO

TO

TO

TO

Pump

Load

Rating*

Wire

50’

100’

200’

300’

400’

500’

Model

HP

Volt

Amps

Amps

Size

WIRE SIZE

115

14.8

20

12

12

12

8

6

6

4

390.262452

1

230

7.4

15

14

14

14

14

14

12

10

115

19.2

25

10

10

10

8

6

4

4

390.262552

1-1/2

230

9.6

15

14

14

14

14

12

10

10

390.262652

2

230

12.0

15

14

14

14

14

12

10

10

*Dual element or Fusetron time delay fuses recommended for all motor circuits.

Содержание HYDRO-GLASS 390.262452

Страница 1: ...Instructions Before First Use of This Product Save This Manual For Future Reference Sears Roebuck and Co Hoffman Estates IL 60179 U S A Safety Instructions Installation Electrical Maintenance Repair...

Страница 2: ...art fires 5 Disconnect electrical power source before installing or working on pump 6 Ground pump with a ground wire run from grounding lug on motor to a grounded lead in the service panel 7 Line volt...

Страница 3: ...void the warranty Check locally for frost protection requirements usually pipe must be 12 below frost line and pump must be insu lated 4 Be sure all pipes and foot valve are clean and in good shape 5...

Страница 4: ...ON 1 Connect the suction pipe to the drive point as illustrated in Figure 6 Keep horizontal pipe run as short as possible Use Teflon tape on male pipe threads Multiple well points may be necessary to...

Страница 5: ...pump 4 Tighten joints hand tight plus 1 1 2 turns Do not over tighten NOTICE Install pump as close to water source as possible Long piping runs and many fittings create friction and re duce flow Use...

Страница 6: ...d copper wire at least as large as power sup ply wires Connect ground wire to grounded lead in service panel metal underground water pipe well casing at least 10 3M long or to ground electrode provide...

Страница 7: ...tal run 10 of horizontal suction pipe 1 of vertical lift due to friction losses in the pipe If no water is produced within 10 minutes stop pump release all pressure remove priming plug refill and try...

Страница 8: ...terminals together see Figure 18 Do not touch metal screwdriver blade or capacitor terminals If in doubt consult a quali fied electrician 4 Unscrew capacitor clamp and remove capacitor Do not disconn...

Страница 9: ...arbon face of seal when passing it over threaded shaft end or shaft shoulder The carbon surface must remain clean or short seal life will result 9 Hold motor shaft with 7 16 open end wrench on shaft f...

Страница 10: ...and re prime If receding water level of pump in well exceeds suction lift a deep well pump is needed 3 Impeller is plugged 3 Clean impeller see Maintenance 4 Check valve or foot valve is stuck 4 Repla...

Страница 11: ...784 2784 2784 7 Impeller C105 92PVB C105 92PBBB C105 214PFA Impeller Screw C30 51SS 8 Diffuser C1 258PCA C1 258PCA 8A Diffuser C1 274P 9 Screw 8 32 RH U30 869SS U30 869SS U30 542SS 1 and 1 1 2 HP 4 Re...

Страница 12: ...reement call 9 am 5 pm Monday Saturday 1 800 827 6655 M A I N T E N A N C E A G R E E M E N T America s Repair Specialists REPAIRSERVICES America s Repair Specialists REPAIRSERVICES America s Repair S...

Отзывы: