background image

INSTALLATION

NOTICE:

Use the installation method below which matches

your well type.

CASED WELL INSTALLATION

1. Inspect foot valve to be sure it works freely. Inspect

strainer to be sure it is clean.

2. Connect foot valve and strainer to the first length of suc-

tion pipe and lower pipe into well. Add sections of pipe
as needed, using Teflon tape on male threads. Be sure that
all suction pipe is leakproof or pump will lose prime and
fail to pump. Install foot valve 10 to 20 feet below the low-
est level to which water will drop while pump is operat-
ing (pumping water level). Your well driller can furnish
this information.

3. To prevent sand and sediment from entering the pump-

ing system, the foot valve/strainer should be at least 5 feet
above the bottom of the well.

4. When the proper depth is reached, install a sanitary well

seal over the pipe and in the well casing. Tighten the bolts
to seal the casing.

5. When using a foot valve, a priming tee and plug as shown

in Figure 5 are recommended.

DUG WELL OR OPEN WATER
INSTALLATION

1. Follow cased well installation, steps 1, 2, 3 and 5.

DRIVEN POINT INSTALLATION

1. Connect the suction pipe to the drive point as illustrated

in Figure 6. Keep horizontal pipe run as short as possible.
Use Teflon tape on male pipe threads. Multiple well
points may be necessary to provide sufficient water to
pump.

2. Install a check valve in piping as shown in Figure 6. Flow

arrow on check valve must point toward pump.

HORIZONTAL PIPING FROM WELL TO
PUMP

1. Never install a suction pipe that is smaller than the suc-

tion tapping of the pump.

2. To aid priming on driven point installations, install a line

check valve as shown in Figure 6. Be sure check valve
flow arrow points toward pump.

DISCHARGE PIPE SIZES

1. If increasing discharge pipe size, install reducer in pump

discharge tapping. Do not increase pipe size by stages.

2. When the pump is set away from the points of water use,

the discharge pipe size should be increased to reduce
pressure losses caused by friction.
• Up to 100’ run: Same size as pump discharge tapping.
• 100’ to 300’ run: Increase one pipe size.
• 300’ to 600’ run: Increase two pipe sizes.

4

Drive
Coupling

Drive
Point

Check
Valve

Drive point
below water
level

Suction Pipe
to Pump

2589 0996

Well
Casing

Foot
Valve

Sanitary
Well Seal

Suction Pipe

10'

Min.

5–10'

Strainer

2590 0996

Priming Tee
and Plug

Figure 5 – Cased/Dug Well Installation

Figure 6 – Driven Point Installation

Содержание HYDRO-GLASS 390.262452

Страница 1: ...Instructions Before First Use of This Product Save This Manual For Future Reference Sears Roebuck and Co Hoffman Estates IL 60179 U S A Safety Instructions Installation Electrical Maintenance Repair...

Страница 2: ...art fires 5 Disconnect electrical power source before installing or working on pump 6 Ground pump with a ground wire run from grounding lug on motor to a grounded lead in the service panel 7 Line volt...

Страница 3: ...void the warranty Check locally for frost protection requirements usually pipe must be 12 below frost line and pump must be insu lated 4 Be sure all pipes and foot valve are clean and in good shape 5...

Страница 4: ...ON 1 Connect the suction pipe to the drive point as illustrated in Figure 6 Keep horizontal pipe run as short as possible Use Teflon tape on male pipe threads Multiple well points may be necessary to...

Страница 5: ...pump 4 Tighten joints hand tight plus 1 1 2 turns Do not over tighten NOTICE Install pump as close to water source as possible Long piping runs and many fittings create friction and re duce flow Use...

Страница 6: ...d copper wire at least as large as power sup ply wires Connect ground wire to grounded lead in service panel metal underground water pipe well casing at least 10 3M long or to ground electrode provide...

Страница 7: ...tal run 10 of horizontal suction pipe 1 of vertical lift due to friction losses in the pipe If no water is produced within 10 minutes stop pump release all pressure remove priming plug refill and try...

Страница 8: ...terminals together see Figure 18 Do not touch metal screwdriver blade or capacitor terminals If in doubt consult a quali fied electrician 4 Unscrew capacitor clamp and remove capacitor Do not disconn...

Страница 9: ...arbon face of seal when passing it over threaded shaft end or shaft shoulder The carbon surface must remain clean or short seal life will result 9 Hold motor shaft with 7 16 open end wrench on shaft f...

Страница 10: ...and re prime If receding water level of pump in well exceeds suction lift a deep well pump is needed 3 Impeller is plugged 3 Clean impeller see Maintenance 4 Check valve or foot valve is stuck 4 Repla...

Страница 11: ...784 2784 2784 7 Impeller C105 92PVB C105 92PBBB C105 214PFA Impeller Screw C30 51SS 8 Diffuser C1 258PCA C1 258PCA 8A Diffuser C1 274P 9 Screw 8 32 RH U30 869SS U30 869SS U30 542SS 1 and 1 1 2 HP 4 Re...

Страница 12: ...reement call 9 am 5 pm Monday Saturday 1 800 827 6655 M A I N T E N A N C E A G R E E M E N T America s Repair Specialists REPAIRSERVICES America s Repair Specialists REPAIRSERVICES America s Repair S...

Отзывы: