Screen 11
Torque op. M1 [10÷100]% (max. current of the motors)
Torque op. M2 [10÷100]% (max. current of the motors)
Torque clo. M1 [10÷100]% (max. current of the motors)
Torque clo. M2 [10÷100]% (max. current of the motors)
Screen 12
Screen 13
Warning lamp Normal/Control/Continuous
Electric lock on/off (on off no comand is given to the electric lock)
Screen 15
List of events it sums up the last 10 events on the control unit
N°8
N°9
N°10
Screen 14
Photo/Timer ON/OFF On ON the PHOTO entry becomes TIMER
Clos. Photo ON/OFF On ON if the photocell is occupied the gate
recloses interrupting the pause
Ped/Timer ON/OFF On ON the PED entry becomes TIMER
Screen 10
Screen 9
Interface relay [OK-NP] (peripheral reveal - not present)
NOTE
: For the respect of the valid European ruels on the safety of the electric gates, it is recommended to not adjust the
parameters
torque Max 1
and
torque Max 2
on the value 100%.
Flashing lamp [OK-NP] (peripheral reveal - not present)
Accelerat. [0÷100]% (inclination of the ramp of acceleration)
Decelerat. [0÷100]% (inclination of the ramp of acceleration)
Leaf delay [0÷12] s. (adjusted leaf delay)
Pedestrian op. [30,50,100]% (percentage pedestrian opening)
Anti-intrusion on/off (in ON it implicates the presence of a contact N.C. on
the limit switch that, if freed, forces the motors in closing
Pre- flashing on/off (activation of the pre-flashing)
Autotest photo. on/off (activates autotest photocell)
Max cycle 0÷100000 (indicates the number of cycles after which it is
necessary to follow up the maintenance)
Photo in opening on/off (activation photocell in opening)
Leaf storke on/off (leaf stroke to release/lock the lock)
It allows to regulate the duration
of the acceleration of the motors on
the start If on 100% the gate will
immediately depart at the max.
adjusted speed
It allows to regulate the duration of
the deceleration of the motors at
the end of opening and closing. If
on 0% the gate won't effect the
phase of deceleration.
Allows to regulate and to visualize
the sensitivity of the anti-sqeezing
With value 100% the
gate in presence of obstacle will
reverse the movement after 5
seconds.
for single leaf and for opening
direction.
If activated in opening it stops
the
automation as long as it is occupied.
When restored in opening the
opening continues, in closing it
reverses the movement.
Normal
:
1 Flash/s in opening
2 Flash/s in closing
On in pause
Control lamp
: the alarm signals
remain until they are eliminated
Continuous
: flashes always also
when gate is not in movement
PROGRAMMER JOLLY PARAMETERS ADJUSTMENT
Diagnostic 10 last events
67410925
17
USER 2 - 24V
International registered trademark n. 2.777.971
REV 02 - 06/2010