Step up Notes
● The maximum height of the drain tube should not exceed 11” above the drain.
● The right angle bend must be within 11.8” of drain. See Figure 15 below.
Within 11.8"
Drain hose(attachment
)
Roof
3.3
-
4
.
9 Ft
Hoisting stand
Below 11"
Drain raising hose
8.66"
Ceiling
clamp (attachment)
Figure 15
● Install the drain hose according to the following process if several drain hoses join together.
See Figure 16 below.
Above 3.94
"
Connect to outside drain.
Always on a downward slope.
The main pipe should have the capacity to carry condensation from all the units.
Figure 16
Check the drain state after installation
● Check the drain operation by pouring 20 oz. of water slowly from the outlet vent or test hole.
● Check the drain operation under cooling
mode after installation is completed.