13.0 Electrical Installation and Commissioning 
 

Connect the power and data connections, and power up the system. For OS2 OSLink, it may be necessary to 
use the install button on the OSLink card to initialize the network. Allow 15 seconds for all devices to report 
the system status. 
 
In case of no function, double check the connections and measure the voltage supplied by the power 
terminals. 
 
Hold the lamp to test the panel. 
To verify the device addressing and mapping, check each device in turn by either activating or simulating a 
fault. 
Remove the protective film from the front panel or leave in place until the building is complete. 
 
 

14.0 Recommended Maintenance 
 

The SHEVTEC Repeater Panel requires no maintenance and contains no replaceable parts. Operation of the 
LEDs and sounder may be tested using the lamp test button. 
 
When cleaning the panel, do not use solvent based or abrasive cleaning products. 

 

15.0 End User Information 
 

Zone Indication 
A Green, Red and Yellow led are allocated to each vent to indicate the following: 

 

 

Green 

Healthy 

Solid 

Has been activated and re-closed, tamper indication * 

On – Short 
Off 

Not Healthy 

Off 

 

 

Red 

Active, actuator not in fire position ** 

Flashing 

Active, vent in fire position 

On Solid 

 

 

Yellow 

Status ( Rainsensor activated, maintenance), Panel Fault 

On Solid 

Fault 

Flashing 

Fault, mains fail 

Short Blink 

 

* OSLoop system with feature enabled only – Insert reset key into underside of the OSLoop MCP to fully 
reset. Not OS2 
** OSLoop only. 

Содержание SHEVTEC

Страница 1: ...SHEVTEC Repeater Panel Technical Information and Operating Instructions...

Страница 2: ...of zone indicators Each zone indication comprises a green healthy yellow fault and red active LED Each zone indication may be controlled by to any OS2 device any zone of an OSLoop system or configured...

Страница 3: ...plate 4 7 0 Binding addresses OS2 4 8 0 Binding addresses OSLoop 4 9 0 Connection to OSLoop Coordinator 5 10 0 Connection to OS2 with OSLink 5 11 0 Address and DIP Switch 7 12 0 Connection to the SHEV...

Страница 4: ...s Torx screwdriver Optional multimeter OSLoop systems require the parameter OADD set this may be preset at the factory or may require use of an SEC POPconfiguration tool 4 0 Preparation SHEVTEC Repeat...

Страница 5: ...e bottom left corner For OS2 bindings this is a single digit number The OSLink addresses set on the OSLink card rotary address switch must beset to match each LED zone After changing OS2 OSlink addres...

Страница 6: ...resetting fuse 10 0 Connection to OS2 with OSLink Ensure the OS2 system is powered down before proceeding Signal Device Terminal FP 4 core and earth 1 5mm OS2 Data A NTA Blue Data B NTB Brown Power V...

Страница 7: ...6 When the cable has an overall screen the screen may optionally be connected to the OS2 SCR terminal...

Страница 8: ...re set off at the factory 12 0 Connection to the SHEVTEC Repeater Panel Connection to the SHEVTEC Repeater Panel is made using a pluggable terminal block CN3 Connections are labelled on the rear of th...

Страница 9: ...mplete 14 0 Recommended Maintenance The SHEVTEC Repeater Panel requires no maintenance and contains no replaceable parts Operation of the LEDs and sounder may be tested using the lamp test button When...

Страница 10: ...he panel audible alarm The alarm override will remain until the cause of the alarm is cleared On OSLoop systems the silence button will also globally silence the local sounders at the coordinators and...

Отзывы: