 6.0 Fixing the mounting plate 

 

The top of the mounting plate is identified by a screw fixing lug. 

 

Ensure the area to mount the panel is flat. Hold the mounting plate up against the surface to which it is to be 

fixed, with the cable coming though the central hole. Check the panel is vertical using a spirit level before marking 

through the holes and remove the plate. 

 

Drill appropriate sized pilot/fixing holes and use plastic plugs/cavity fixings where appropriate to fix the mounting 
plate. 

 

  7.0 Binding addresses (OS2) 

 

 

 

 

 

 

 

 

 

 

 

     

   8.0  Binding addresses (OSloop

 

 

 

 

 

 

 

 

 

 

 

 

 

The binding addresses of the panel are pre-configured at the factory 

and for each indicator it is printed in the bottom left corner. For OS2 

bindings, this is a single digit number. 
 
The OSLink addresses set on the OSLink card rotary address 

switch must be set to match each LED zone. 
 
After changing OS2 OSlink address, the network must be restarted 

using the install button on the OSLink card. 

 

 

 

 

The binding address for each indicator it is printed in the bottom 

left corner. For OSLoop bindings, this is a dotted address. 
 
The binding contains the address of the coordinator and a sub-

address of the OSLoop MCP. For example 1.0 refers to OSLoop 

coordinator at address 1 with MCP at zone switch set to 0. 
 

If not already set, each OSLoop coordinator needs to have the 

OSLink address set using a POP configuration tool (Parameters-

>OSLink-> OADD). After changing this parameter, it is necessary 

to reset the coordinator. 
 

Ensure the MCP zone switches are correctly set to match the sub-address. 

 

Содержание SHEVTEC

Страница 1: ...SHEVTEC Repeater Panel Technical Information and Operating Instructions...

Страница 2: ...of zone indicators Each zone indication comprises a green healthy yellow fault and red active LED Each zone indication may be controlled by to any OS2 device any zone of an OSLoop system or configured...

Страница 3: ...plate 4 7 0 Binding addresses OS2 4 8 0 Binding addresses OSLoop 4 9 0 Connection to OSLoop Coordinator 5 10 0 Connection to OS2 with OSLink 5 11 0 Address and DIP Switch 7 12 0 Connection to the SHEV...

Страница 4: ...s Torx screwdriver Optional multimeter OSLoop systems require the parameter OADD set this may be preset at the factory or may require use of an SEC POPconfiguration tool 4 0 Preparation SHEVTEC Repeat...

Страница 5: ...e bottom left corner For OS2 bindings this is a single digit number The OSLink addresses set on the OSLink card rotary address switch must beset to match each LED zone After changing OS2 OSlink addres...

Страница 6: ...resetting fuse 10 0 Connection to OS2 with OSLink Ensure the OS2 system is powered down before proceeding Signal Device Terminal FP 4 core and earth 1 5mm OS2 Data A NTA Blue Data B NTB Brown Power V...

Страница 7: ...6 When the cable has an overall screen the screen may optionally be connected to the OS2 SCR terminal...

Страница 8: ...re set off at the factory 12 0 Connection to the SHEVTEC Repeater Panel Connection to the SHEVTEC Repeater Panel is made using a pluggable terminal block CN3 Connections are labelled on the rear of th...

Страница 9: ...mplete 14 0 Recommended Maintenance The SHEVTEC Repeater Panel requires no maintenance and contains no replaceable parts Operation of the LEDs and sounder may be tested using the lamp test button When...

Страница 10: ...he panel audible alarm The alarm override will remain until the cause of the alarm is cleared On OSLoop systems the silence button will also globally silence the local sounders at the coordinators and...

Отзывы: