![SE Controls SHEVTEC Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/se-controls/shevtec/shevtec_technical-information-and-operating-instructions_1220621002.webp)
1
Application.
The SHEVTEC® SHEVTEC® Repeater Panel provides a low cost, semi-custom solution for reporting the status for
S.E.Controls smoke ventilation installations. The system was designed to work with OS2 OSLink and OSLoop
systems. Currently OS1.75 and OS2 OSLon are not supported.
The SHEVTEC® Repeater Panel is implemented using modular construction. The size of the panel is matched to
the job requirements, from four to twelve rows of indicators as standard. The indicators are arranged in a grid
of three columns which allows buildings with one, two or three smokestacks to be represented. For large and
complex installations, more than one panel may be used.
Every panel features four rows by three columns of zone indicator, six status indicators and three
programmable touch buttons. Two extension panels may be used, each adding two or four rows of zone
indicators.
Each zone indication comprises a green (healthy), yellow (fault), and red (active) LED. Each zone indication may
be controlled by to any OS2 device, any zone of an OSLoop system or configured as disabled.
In addition, six LED groups at bottom of the panel may be programmed for special or global functions such as
‘mains fail’ or ‘maintenance due’. Any LEDs that are not required may be configured as disabled.
Three capacitive touch buttons are provided and maybe configured to allow user input. ‘Silence’ and ‘lamp-test’
are the most common use of these buttons.
The panel is simple to install, requiring a four wire connection to the power and data. Power with battery
backup protection is provided from an OS2 or OSLoop Coordinator, so no mains power is required at the panel.
A fixing plate and locking screw ensure that the panel is easily and securely fitted to the wall.
Power.
Supply 18-30V D.C. 100mA
from external battery
backed source
Environment.
Rating IP20 Humidity Range 10
to 90%
Non- Condensing
Operating temp -10 to +50°C
Storage -20 to + 75°C