9.0 Connection to OSLoop Coordinator
The OSLOOP coordinator has an OSLink repeater comms connector CN3 supplying both data and SHEVTEC®
Repeater Panel. NA and NB connections are duplicated to allow daisy-chaining of devices.
Signal
Device Terminal
FP+4 core and earth
1.5mm
Data A
NA
Blue
Data B
NB
Brown
Power V+
VC+
Black
Power 0V
OV
Grey
Current drawn from VC+ should not exceed 400mA and is protected by a self-resetting fuse.
10.0 Connection to OS2 with OSLink
Ensure the OS2 system is powered down before proceeding.
Signal
Device Terminal
FP+4 core and earth
1.5mm
OS2
Data A
NTA
Blue
Data B
NTB
Brown
Power V+
PER
Black
Power 0V
OVA
Grey
The colour scheme used must be consistent across the installation. The table above shows suggested colour
codes for various cables. Where the construction is two twisted pairs, the data and power should be on
separate pairs.
Current drawn from an OS2 PER terminal is limited by fuse FH2 (Nominally 200mA). This fuse may be uprated
if multiple smoke detectors or other loads on per are used.