 9.0  Connection to OSLoop Coordinator 

The OSLOOP coordinator has an OSLink repeater comms connector CN3 supplying both data and SHEVTEC® 

Repeater Panel. NA and NB connections are duplicated to allow daisy-chaining of devices. 

 

 

Signal 

Device Terminal

 

 

FP+4 core and earth 

1.5mm

 

 

Data A 

NA 

 

Blue 

Data B 

NB 

 

Brown 

Power V+ 

VC+ 

 

Black 

Power 0V 

OV 

 

Grey 

 

Current drawn from VC+ should not exceed 400mA and is protected by a self-resetting fuse. 

 

10.0 Connection to OS2 with OSLink 

Ensure the OS2 system is powered down before proceeding. 
 

Signal 

Device Terminal

 

 

FP+4 core and earth 

1.5mm

 

 

OS2

 

 

Data A 

NTA 

 

Blue 

Data B 

NTB 

 

Brown 

Power V+ 

PER 

 

Black 

Power 0V 

OVA 

 

Grey 

 

The colour scheme used must be consistent across the installation. The table above shows suggested colour 

codes for various  cables. Where the construction is two twisted pairs, the data and power should be on   

separate pairs. 
Current drawn from an OS2 PER terminal is limited by fuse FH2 (Nominally 200mA). This fuse may be uprated 

if multiple smoke detectors or other loads on per are used.

Содержание SHEVTEC

Страница 1: ...SHEVTEC Repeater Panel Technical Information and Operating Instructions...

Страница 2: ...of zone indicators Each zone indication comprises a green healthy yellow fault and red active LED Each zone indication may be controlled by to any OS2 device any zone of an OSLoop system or configured...

Страница 3: ...plate 4 7 0 Binding addresses OS2 4 8 0 Binding addresses OSLoop 4 9 0 Connection to OSLoop Coordinator 5 10 0 Connection to OS2 with OSLink 5 11 0 Address and DIP Switch 7 12 0 Connection to the SHEV...

Страница 4: ...s Torx screwdriver Optional multimeter OSLoop systems require the parameter OADD set this may be preset at the factory or may require use of an SEC POPconfiguration tool 4 0 Preparation SHEVTEC Repeat...

Страница 5: ...e bottom left corner For OS2 bindings this is a single digit number The OSLink addresses set on the OSLink card rotary address switch must beset to match each LED zone After changing OS2 OSlink addres...

Страница 6: ...resetting fuse 10 0 Connection to OS2 with OSLink Ensure the OS2 system is powered down before proceeding Signal Device Terminal FP 4 core and earth 1 5mm OS2 Data A NTA Blue Data B NTB Brown Power V...

Страница 7: ...6 When the cable has an overall screen the screen may optionally be connected to the OS2 SCR terminal...

Страница 8: ...re set off at the factory 12 0 Connection to the SHEVTEC Repeater Panel Connection to the SHEVTEC Repeater Panel is made using a pluggable terminal block CN3 Connections are labelled on the rear of th...

Страница 9: ...mplete 14 0 Recommended Maintenance The SHEVTEC Repeater Panel requires no maintenance and contains no replaceable parts Operation of the LEDs and sounder may be tested using the lamp test button When...

Страница 10: ...he panel audible alarm The alarm override will remain until the cause of the alarm is cleared On OSLoop systems the silence button will also globally silence the local sounders at the coordinators and...

Отзывы: