11.0 Address and DIP Switch 

 

      The rear of the repeater has a four-way DIP switch and a rotary address switch. 
 

   Rotary address which selects the OSLink address of the panel in the range 0-15. This should be pre-set in the     

factory when the panel is programmed. Unless there are multiple panels, the address is likely to be zero. 

 

The Dipswitch SW1 on the back of the SHEVTEC

®

 Repeater Panel has four configuration switches. 

 

Switch

 

Function

 

 

Terminator 

Used to place a line terminating resistor on the communications line. Leave 

this switched off unless advised by SEC technical staff. 

Silence 

Switch on to disable the SHEVTEC® Repeater Panel sounder. 

Test 

Always off 

16 

Allows oslink addresses 16-31 to be used. Should be pre-set off at the factory. 

 

 

 

 

12.0 Connection to the SHEVTEC® Repeater Panel 
 

Connection to the SHEVTEC® Repeater Panel is made using a pluggable terminal block (CN3). Connections 
are labelled on the rear of the panel. 
 

Signal 

Device Terminal

 

 

FP + 4 core and earth 

1.5mm

 

 

Data A 

 

Blue 

Data B 

 

Brown 

Power V+ 

 

Black 

Power 0V 

OV 

 

Grey 

 
Strip back the cable and remove any cable screen, using tape if necessary, leaving a reasonable spare length 
of cable to allow mounting and removal of the panel, undo the screws which retain CN3 and remove the free 
part of the connector. Connect the four wires. 
 
If the panel is not at the end of a network, it may be necessary to connect more than one cable. If possible, 
common the connections at the pluggable connector. Otherwise use a separate terminal block. 
 
Plug in the CN3 connector and screw with the connector retaining screws. 
Hook the panel onto the black plate and secure with the torx tamperproof screw. 
 
 
 
 
 
 
 

Содержание SHEVTEC

Страница 1: ...SHEVTEC Repeater Panel Technical Information and Operating Instructions...

Страница 2: ...of zone indicators Each zone indication comprises a green healthy yellow fault and red active LED Each zone indication may be controlled by to any OS2 device any zone of an OSLoop system or configured...

Страница 3: ...plate 4 7 0 Binding addresses OS2 4 8 0 Binding addresses OSLoop 4 9 0 Connection to OSLoop Coordinator 5 10 0 Connection to OS2 with OSLink 5 11 0 Address and DIP Switch 7 12 0 Connection to the SHEV...

Страница 4: ...s Torx screwdriver Optional multimeter OSLoop systems require the parameter OADD set this may be preset at the factory or may require use of an SEC POPconfiguration tool 4 0 Preparation SHEVTEC Repeat...

Страница 5: ...e bottom left corner For OS2 bindings this is a single digit number The OSLink addresses set on the OSLink card rotary address switch must beset to match each LED zone After changing OS2 OSlink addres...

Страница 6: ...resetting fuse 10 0 Connection to OS2 with OSLink Ensure the OS2 system is powered down before proceeding Signal Device Terminal FP 4 core and earth 1 5mm OS2 Data A NTA Blue Data B NTB Brown Power V...

Страница 7: ...6 When the cable has an overall screen the screen may optionally be connected to the OS2 SCR terminal...

Страница 8: ...re set off at the factory 12 0 Connection to the SHEVTEC Repeater Panel Connection to the SHEVTEC Repeater Panel is made using a pluggable terminal block CN3 Connections are labelled on the rear of th...

Страница 9: ...mplete 14 0 Recommended Maintenance The SHEVTEC Repeater Panel requires no maintenance and contains no replaceable parts Operation of the LEDs and sounder may be tested using the lamp test button When...

Страница 10: ...he panel audible alarm The alarm override will remain until the cause of the alarm is cleared On OSLoop systems the silence button will also globally silence the local sounders at the coordinators and...