7
11.0 Address and DIP Switch
The rear of the repeater has a four-way DIP switch and a rotary address switch.
Rotary address which selects the OSLink address of the panel in the range 0-15. This should be pre-set in the
factory when the panel is programmed. Unless there are multiple panels, the address is likely to be zero.
The Dipswitch SW1 on the back of the SHEVTEC
®
Repeater Panel has four configuration switches.
Switch
Function
1
Terminator
Used to place a line terminating resistor on the communications line. Leave
this switched off unless advised by SEC technical staff.
2
Silence
Switch on to disable the SHEVTEC® Repeater Panel sounder.
3
Test
Always off
4
16
Allows oslink addresses 16-31 to be used. Should be pre-set off at the factory.
12.0 Connection to the SHEVTEC® Repeater Panel
Connection to the SHEVTEC® Repeater Panel is made using a pluggable terminal block (CN3). Connections
are labelled on the rear of the panel.
Signal
Device Terminal
FP + 4 core and earth
1.5mm
Data A
A
Blue
Data B
B
Brown
Power V+
+
Black
Power 0V
OV
Grey
Strip back the cable and remove any cable screen, using tape if necessary, leaving a reasonable spare length
of cable to allow mounting and removal of the panel, undo the screws which retain CN3 and remove the free
part of the connector. Connect the four wires.
If the panel is not at the end of a network, it may be necessary to connect more than one cable. If possible,
common the connections at the pluggable connector. Otherwise use a separate terminal block.
Plug in the CN3 connector and screw with the connector retaining screws.
Hook the panel onto the black plate and secure with the torx tamperproof screw.