Example of screen showing "max. battery voltage" alarm designated 08-00 and "emergency stop" fault

designated 00-11.

The alarms and faults are displayed in the same way as for versions 0.01B and 1.04D:

-

Up to two codes (max.) displayed on screen

-

Fault takes priority over alarm

-

Faults are reset in order of appearance

For more details, refer to paragraph 8.

All the alarms and faults which can appear on the MICS Telys screen are listed in the table below.a.

_____________________________________________________________________________________________________Appendix - software version 1.05e: "international" language

(símbolos 3) %    

 

(símbolos 4) RPM  

 

(símbolos 5) Volts  

 

        

00-1

 

        

08-0

   

 

24.2 

50 

0

Wording 

Alarm 

Fault 

Generated on  

Generator set emergency stop  

impossible 

00-1 

CB, CB12 

External emergency stop  

impossible 

01-1 

CB, CB12 

Engine oil pressure  

impossible 

02-1 

CB, CB12 

Engine water temperature  

impossible 

03-1 

CB, CB12 

Daily fuel tank leve l low 

04-0 

04-1 

CB, CB12 

Radiator water level low  

impossible 

05-1 

CB, CB12 

Alternator overload or short -circuit 

06-0 

06-1 

CB, CB12 

Engine overspeed  

impossible 

07-1 

CB, CB12 

Min. battery voltage  

08-0 

08-1 

CB, CB12 

Max. battery voltage  

09-0 

09-1 

CB, CB12 

Lithium battery absent  

10-0 

impossible 

CB, CB12 

Generator set no start  

impossible 

11-1 

CB, CB12 

Min. alternator voltage  

12-0 

12-1 

CB, CB12 

Max. alternator voltage  

13-0 

13-1 

CB, CB12 

Min. alternator frequency  

14-0 

14-1 

CB, CB12 

Max. alternator frequ ency 

15-0 

15-1 

CB, CB12 

Option 3 module CAN bus  

impossible 

16-1 

CB, CB12 

Option 4 module CAN bus  

impossible 

17-1 

CB12 

Option 5 module CAN bus  

impossible 

18-1 

CB12 

Option 6 module CAN bus  

impossible 

19-1 

CB12 

Spare 

 

 

 

RS485 communication  

21-1 

impossible 

CB, CB12 

Hardware watchdog  

impossible 

22-1 

CB, CB12 

Spare 

 

 

 

Spare 

 

 

 

Normal contactor open (system side)  

25-0 

impossible 

CB, CB12 

Emergency contactor open (generating set side)  

26-0 

impossible 

CB, CB12 

Oil temperature  

impossible 

27-1 

CB, CB12 

Oil level low  

impossible 

28-1 

CB12 

No water preheating  

29-0 

29-1 

CB12 

Differential trigger  

30-0 

30-1 

CB12 

Permanent insulation monitor trigger  

31-0 

31-1 

CB12 

Differential relay connection  

impossible 

32-1 

CB12 

Permanent insulation monitor connection  

impossible 

33-1 

CB12 

Battery charger fault  

34-0 

34-1 

CB12 

Air cooler trip  

impossible 

35-1 

CB12 

Air cooler low level  

impossible 

36-1 

CB12 

Fuel pump 1 trip  

37-0 

37-1 

CB12 

Retention tank  

38-0 

38-1 

CB12 

Fuel tank low level  

39-0 

39-1 

CB12 

Water flow 

impossible 

40-1 

module 3 

Fire detection  

impossible 

41-1 

module 3 

Oil leak  

impossible 

42-1 

module 3 

Fuel leak 

impossible 

43-1 

module 3 

Air cooler compartment door open  

impossible 

44-1 

module 3 

MCPS door open  

impossible 

45-1 

module 3 

Main circuit breaker open  

46-0 

46-1 

module 3 

Overload 

47-0 

impossible 

CB12 

Содержание MICS Telys

Страница 1: ...Instructions for use Telys level 1 1 06 F R f constructeur R f GPAO 33502012701 ind1...

Страница 2: ...GB ENGLISH S SA AF FE ET TY Y S SY YM MB BO OL LS S 4 4 C CO ON NT TE EN NT TS S 1 1 10 01 3...

Страница 3: ...ing parts risk of entanglement Caution risk of corrosion Caution risk of explosion Caution refer to the publications supplied with the Genset Authorised personnel only M MA AC CH HI IN NE ER RY Y D DI...

Страница 4: ...10 01 5 _____________________________________________________________________________________________________________________________________________________...

Страница 5: ...set programmable control ler M MI IC CS S A AM MP PG G Device for electrical value display P Po ot te en nt ti io om me et te er r v vo ol lt ts s Adjusts the alternator voltage D Du ua al l f fr r q...

Страница 6: ...w without p prior n notice All r rights r reserved a as c concerns c changes t to t these m manuals Reproduction o or t translation i in w whole o or p part s strictly p prohibited w without p prior w...

Страница 7: ...repeatedly pressing the I P key will only display the voltages o The change from the F key to the F H key does not affect the information displayed on the screen p The most significant change is that...

Страница 8: ...cess code Option 4 of module 4 allowing operation at three different voltages 480V 208V and 240V may be fine tuned to reflect the customer s actual usage The low coolant level LED of the optional modu...

Страница 9: ...8 2 Removing messages on screen 49 9 Displaying the status messages 49 10 Accessing the level 1 display 50 11 Alarm Flt menu 51 11 1 Special features for a fault 51 11 2 Special features for an alarm...

Страница 10: ...to select Manu mode with LED Button to open genset breaker with LED Button to select Manu mode with LED Button to close genset breaker with LED Button to test the LEDs except ON button LED 1 Oil pres...

Страница 11: ...voltage drop at start up All connections are built into the printed circuit board on both sides with full screen printing 4 4 L Lo og gi ic ca al l a an na al lo og g I I O O All inputs and outputs a...

Страница 12: ...nts 9 9 M Ma ai in ns s v vo ol lt ta ag ge e m ma ai in ns s 2 2 2 wire 1ph neutral unisolated with 10A 240Vac built in power bus in 50 and 60Hz No voltage and frequency measurements 1 10 0 C Ch ha a...

Страница 13: ...witch selection for VDE option 2 20 0 E En nv vi ir ro on nm me en nt t a an nd d s st ta an nd da ar rd ds s Operating temperature 15 C to 60 C Storage temperature 20 C to 70 C Resistance to shocks I...

Страница 14: ...UTIL C35 UTIL AC DC DC DC AC AC 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 V J N 30 31 1 2 1 2 3 4 5 6 7 8 9 10 11 12 External command mains sensing or client contact Output C B f...

Страница 15: ...r positioned over English Pressing Esc configures the control unit in English Any messages will appear be in English If neither V nor Esc is pressed the overview screen see paragraph 1 7 appears autom...

Страница 16: ...e will be no digital indication on screen However the wording Fuel L Lev will appear see also paragraph 5 This particular display is used to perform a quick diagnostic on the physical status of the in...

Страница 17: ...only if the green LED is ON see paragraph 18 The operator still has control over the Normal EmergencyY switch and the generator set If an external Start command appears on the screen the control unit...

Страница 18: ...in sleep mode the various indications stay visible on screen Genset stopped with no external command no EJP start up and no clock activation If one the system logical inputs changes status alarm faul...

Страница 19: ...phase 1 and neutral V2 voltage across phase 2 and neutral V3 voltage across phase 3 and neutral Press U V again to bring up the first screen and so on Ph neutr V1 voltages V2 Volts V3 ext command 1 17...

Страница 20: ...3 p phase w without n neutral 3ph Press I to get the three phase currents I1 current in phase 1 I2 current in phase 2 I3 current in phase 3 If you press I again nothing changes Phase I1 current I2 Am...

Страница 21: ...enheit F The third line indicates the water temperature expressed in degrees Fahrenheit F Oil Pr PSI Oil T F WaterT F ext command 1 17 15 gen running 12 01 00 167 90 1 194 Screen 3 3 Press Engine a th...

Страница 22: ...E A ALARM A AND F FAULT M MESSAGES All alarms and faults are clearly viewed on screen Two lines are dedicated for their display see screens below 8 8 1 1 A Ap pp pe ea ar ra an nc ce e o of f m me es...

Страница 23: ...reset the low fuel level fault the message disappears Ph ph U12 0 voltages U23 0 Volts U31 0 Fault Low Fuel Level Fault Emergency Stop ext command 1 17 45 gen stopped 12 01 00 The message Fault m modu...

Страница 24: ...e Press to move the cursor to the next sign on the right hand side if possible or to the next line Press to move the cursor to the previous sign if possible or to the previous line By pressing or the...

Страница 25: ...being the biggest number or in other words from the oldest to the newest message The messages are always displayed two at a time see the two screens below The left hand side screen shows messages num...

Страница 26: ...u Auto Test ATS Mains Stand by changeover control 0 and 1 in Manu mode only ON button Also the automatic power up automatic shutdown and logical status of option No 20 input on option 4 module shutdow...

Страница 27: ...10 11 12 0 1 Input 1 Diff or C I C trip Option 3 3 M Module Logical status display of the inputs on option 3 module i e the eight inputs described in Section Tech nical characteristies OPTION 3 MODUL...

Страница 28: ...e inputs of the option 5 module are displayed programmed with Volvo D12 engine Display of logical status of inputs of option 5 module For the Volvo D12 engine only inputs 1 2 and 3 are used Note The a...

Страница 29: ...TS screens to display the logical status of the inputs and outputs of the module in accordance with its programming Composition o of t the i interface b boards logical o outputs CB board 7 outputs CB1...

Страница 30: ...uts on option 3 module As these outputs can be programmed the wording on each line varies according to the programming performed For that reason the wording does not appear on the screen opposite OPTI...

Страница 31: ...follows CONTRAST Esc Exit down up Current Value 148 Adjust contrast Min Value 1 Max Value 250 16 P PROTECT M MENU If a protection of differential type differential relay or via constant insulation che...

Страница 32: ...ro ol l The fuel solenoid control activation is interlocked with the engine preglow control or starter control activation The fuel solenoid supply is then permanent It is interrupted when the engine...

Страница 33: ...non in any regulation system When the engine reaches the electrical or pneumatic starter trip ping threshold the engine speed and alternator voltage stabilisation process is launched When the delay el...

Страница 34: ...d with the factory standard configuration 1 19 9 1 1 I In n S St to op p m mo od de e When is positioned in Stop mode the Mains contactor is closed mains available and the 0 button LED is lit The Main...

Страница 35: ...stantly the Stand by contactor the 1 button LED goes out and the message of toggling from Stand by to Mains appears When the delay elapses the Mains contactor closes automatically the message Mains c...

Страница 36: ...4 D Di is sp pl la ay y o of f e el le ec ct tr ri ic ca al l v va al lu ue es s To facilitate understanding the electrical values are not represented by pictograms Press the U V button to display th...

Страница 37: ...For more information on the meaning of the notations refer to the user paragraph 5 A third screen can be accessed using the Engine button with Anglo Saxon notations for the oil pressure PSI the water...

Страница 38: ...The cooling time delay parameter 10 of timing menu is displayed next to the symbol and decrements automatically from the adjustment setting to 0 Example of screen showing that three minutes and ten s...

Страница 39: ...sible 11 1 CB CB12 Min alternator voltage 12 0 12 1 CB CB12 Max alternator voltage 13 0 13 1 CB CB12 Min alternator frequency 14 0 14 1 CB CB12 Max alternator frequ ency 15 0 15 1 CB CB12 Option 3 mod...

Страница 40: ...gine overspeed impossible 53 1 module 5 QST30 engine general fault impossible 54 1 module 5 QST30 engine general alarm 55 0 impossible module 5 Engine oil high level 56 0 impossible module 4 Engine oi...

Отзывы: