___________________________________________________________________________________________________________________________________________ATS operation

The screen opposite indicates the delay for the Mains contactor to toggle to the Stand-by contactor.
When the delay elapses, the Stand-by contactor closure is requested, the message Stand-bby cclosed
appears, the 1 button LED comes on and the genset then delivers the installation (see paragraph
17.7).

Ph./ph.     U12

voltages     U23

(Volts)        U31

toggle delay

    

  

mains->stand-by:      05’’

398

399

400

When the external command disappears, the mains return delay begins (if type 2 selected) and the
screen opposite appears.
When the mains return delay elapses, the Stand-by contactor opens and the 1 button LED goes out.

Phase          I1

current       I2

(Amps)        I3

ext command=0

mains return:       00’ 60’’

436

425

420

The message on the screen opposite appears to indicate that the Mains contactor will close in x
seconds.
When the delay elapses, the Mains contactor closure is requested, the message Mains  cclosed
appears, the 0 button LED comes on and the mains delivers the installation again.

Note 1: in cases where the contactors feed back data is ignored, the toggling messages from one contactor
to the other (M S and S M) do not appear.
Note 2: in cases of a type 1 start (the control unit built-in mains return delay ignored), the message mains

return: 000' 660'' on the previous screen does not appear.

Phase          I1

current       I2

(Amps)        I3

toggle delay

stand-by->mains:      05’’

0

0
0

1199..33.. IInn m

maannuuaall m

mooddee

The ATS can only operate in Manu mode when the green LED is lit.
Press button 1 to close the Stand-by contactor. Before the Stand-by contactor closes, the Mains contactor opens, the 0 button LED goes out and the
message of toggling from Mains to Stand-by appears. When the delay elapses, the Stand-by contactor closure is effective, the message Stand-bby

closed appears and the 1 button LED comes on.
Press button 0 to open (instantly) the Stand-by contactor, the 1 button LED goes out and the message of toggling from Stand-by to Mains appears.
When the delay elapses, the Mains contactor closes automatically, the message Mains cclosed appears and the 0 button LED comes on.

APPENDIX - SOFTWARE VERSION 1.05E: "INTERNATIONAL" LANGUAGE

11 - IInnttrroodduuccttiioonn

Software version 1.05E used with interface boards CB and CB12 enable you to use the MICS Telys in a language which is different from the four stan-
dard languages already implemented. This language is based on the use of pictograms. Compatibility is ensured with the old interface boards. This
means it is possible to reprogram, on site, an interface board having software index 1.01B or 1.04D with a software having an index 1.05E. Howe-
ver, use of a software version 1.05E requires a display defined for software version 1.2 (see paragraph 2).

22 - SSttaarrttiinngg uupp tthhee M

MIIC

CSS TTeellyyss

When the MICS Telys is powered up, the initialization screen indicates the display software version.

The initialization phase takes no more than 5 seconds.

Note: A display flashed to version 1.2 can be used with no problem with an interface board version 2.01B or
1.04D.

Next, the language selection screen is displayed. The cursor flashes by default on "International". If no action is taken while the four squares are dis-

played in the small overlaid window, the MICS Telys automatically goes to the international language.

You then have around 6 seconds to change the language by pressing the 

button then the V or Esc (*) but-

tons.

(*)

By pressing the V button, the selected language is stored, meaning that the next time the unit is powe-

red up, the cursor will automatically go to the previously selected language. In addition, by pressing the V but-

ton, the system goes to the next screen to modify the date and time.
(*) If you press the Esc key, the selected language is not stored in memory. The next time the unit is powered up, the cursor will automatically be posi-
tioned on the international language.

 

Version 1.2

LANGUAGE SELECTION 

V: 

 

Valid   

 

Esc: Exit

 

o International

 

o English

 

 

Spanish

 

 

Portugues

o French

 

Содержание MICS Telys

Страница 1: ...Instructions for use Telys level 1 1 06 F R f constructeur R f GPAO 33502012701 ind1...

Страница 2: ...GB ENGLISH S SA AF FE ET TY Y S SY YM MB BO OL LS S 4 4 C CO ON NT TE EN NT TS S 1 1 10 01 3...

Страница 3: ...ing parts risk of entanglement Caution risk of corrosion Caution risk of explosion Caution refer to the publications supplied with the Genset Authorised personnel only M MA AC CH HI IN NE ER RY Y D DI...

Страница 4: ...10 01 5 _____________________________________________________________________________________________________________________________________________________...

Страница 5: ...set programmable control ler M MI IC CS S A AM MP PG G Device for electrical value display P Po ot te en nt ti io om me et te er r v vo ol lt ts s Adjusts the alternator voltage D Du ua al l f fr r q...

Страница 6: ...w without p prior n notice All r rights r reserved a as c concerns c changes t to t these m manuals Reproduction o or t translation i in w whole o or p part s strictly p prohibited w without p prior w...

Страница 7: ...repeatedly pressing the I P key will only display the voltages o The change from the F key to the F H key does not affect the information displayed on the screen p The most significant change is that...

Страница 8: ...cess code Option 4 of module 4 allowing operation at three different voltages 480V 208V and 240V may be fine tuned to reflect the customer s actual usage The low coolant level LED of the optional modu...

Страница 9: ...8 2 Removing messages on screen 49 9 Displaying the status messages 49 10 Accessing the level 1 display 50 11 Alarm Flt menu 51 11 1 Special features for a fault 51 11 2 Special features for an alarm...

Страница 10: ...to select Manu mode with LED Button to open genset breaker with LED Button to select Manu mode with LED Button to close genset breaker with LED Button to test the LEDs except ON button LED 1 Oil pres...

Страница 11: ...voltage drop at start up All connections are built into the printed circuit board on both sides with full screen printing 4 4 L Lo og gi ic ca al l a an na al lo og g I I O O All inputs and outputs a...

Страница 12: ...nts 9 9 M Ma ai in ns s v vo ol lt ta ag ge e m ma ai in ns s 2 2 2 wire 1ph neutral unisolated with 10A 240Vac built in power bus in 50 and 60Hz No voltage and frequency measurements 1 10 0 C Ch ha a...

Страница 13: ...witch selection for VDE option 2 20 0 E En nv vi ir ro on nm me en nt t a an nd d s st ta an nd da ar rd ds s Operating temperature 15 C to 60 C Storage temperature 20 C to 70 C Resistance to shocks I...

Страница 14: ...UTIL C35 UTIL AC DC DC DC AC AC 6 1 2 3 4 5 1 2 3 4 5 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 V J N 30 31 1 2 1 2 3 4 5 6 7 8 9 10 11 12 External command mains sensing or client contact Output C B f...

Страница 15: ...r positioned over English Pressing Esc configures the control unit in English Any messages will appear be in English If neither V nor Esc is pressed the overview screen see paragraph 1 7 appears autom...

Страница 16: ...e will be no digital indication on screen However the wording Fuel L Lev will appear see also paragraph 5 This particular display is used to perform a quick diagnostic on the physical status of the in...

Страница 17: ...only if the green LED is ON see paragraph 18 The operator still has control over the Normal EmergencyY switch and the generator set If an external Start command appears on the screen the control unit...

Страница 18: ...in sleep mode the various indications stay visible on screen Genset stopped with no external command no EJP start up and no clock activation If one the system logical inputs changes status alarm faul...

Страница 19: ...phase 1 and neutral V2 voltage across phase 2 and neutral V3 voltage across phase 3 and neutral Press U V again to bring up the first screen and so on Ph neutr V1 voltages V2 Volts V3 ext command 1 17...

Страница 20: ...3 p phase w without n neutral 3ph Press I to get the three phase currents I1 current in phase 1 I2 current in phase 2 I3 current in phase 3 If you press I again nothing changes Phase I1 current I2 Am...

Страница 21: ...enheit F The third line indicates the water temperature expressed in degrees Fahrenheit F Oil Pr PSI Oil T F WaterT F ext command 1 17 15 gen running 12 01 00 167 90 1 194 Screen 3 3 Press Engine a th...

Страница 22: ...E A ALARM A AND F FAULT M MESSAGES All alarms and faults are clearly viewed on screen Two lines are dedicated for their display see screens below 8 8 1 1 A Ap pp pe ea ar ra an nc ce e o of f m me es...

Страница 23: ...reset the low fuel level fault the message disappears Ph ph U12 0 voltages U23 0 Volts U31 0 Fault Low Fuel Level Fault Emergency Stop ext command 1 17 45 gen stopped 12 01 00 The message Fault m modu...

Страница 24: ...e Press to move the cursor to the next sign on the right hand side if possible or to the next line Press to move the cursor to the previous sign if possible or to the previous line By pressing or the...

Страница 25: ...being the biggest number or in other words from the oldest to the newest message The messages are always displayed two at a time see the two screens below The left hand side screen shows messages num...

Страница 26: ...u Auto Test ATS Mains Stand by changeover control 0 and 1 in Manu mode only ON button Also the automatic power up automatic shutdown and logical status of option No 20 input on option 4 module shutdow...

Страница 27: ...10 11 12 0 1 Input 1 Diff or C I C trip Option 3 3 M Module Logical status display of the inputs on option 3 module i e the eight inputs described in Section Tech nical characteristies OPTION 3 MODUL...

Страница 28: ...e inputs of the option 5 module are displayed programmed with Volvo D12 engine Display of logical status of inputs of option 5 module For the Volvo D12 engine only inputs 1 2 and 3 are used Note The a...

Страница 29: ...TS screens to display the logical status of the inputs and outputs of the module in accordance with its programming Composition o of t the i interface b boards logical o outputs CB board 7 outputs CB1...

Страница 30: ...uts on option 3 module As these outputs can be programmed the wording on each line varies according to the programming performed For that reason the wording does not appear on the screen opposite OPTI...

Страница 31: ...follows CONTRAST Esc Exit down up Current Value 148 Adjust contrast Min Value 1 Max Value 250 16 P PROTECT M MENU If a protection of differential type differential relay or via constant insulation che...

Страница 32: ...ro ol l The fuel solenoid control activation is interlocked with the engine preglow control or starter control activation The fuel solenoid supply is then permanent It is interrupted when the engine...

Страница 33: ...non in any regulation system When the engine reaches the electrical or pneumatic starter trip ping threshold the engine speed and alternator voltage stabilisation process is launched When the delay el...

Страница 34: ...d with the factory standard configuration 1 19 9 1 1 I In n S St to op p m mo od de e When is positioned in Stop mode the Mains contactor is closed mains available and the 0 button LED is lit The Main...

Страница 35: ...stantly the Stand by contactor the 1 button LED goes out and the message of toggling from Stand by to Mains appears When the delay elapses the Mains contactor closes automatically the message Mains c...

Страница 36: ...4 D Di is sp pl la ay y o of f e el le ec ct tr ri ic ca al l v va al lu ue es s To facilitate understanding the electrical values are not represented by pictograms Press the U V button to display th...

Страница 37: ...For more information on the meaning of the notations refer to the user paragraph 5 A third screen can be accessed using the Engine button with Anglo Saxon notations for the oil pressure PSI the water...

Страница 38: ...The cooling time delay parameter 10 of timing menu is displayed next to the symbol and decrements automatically from the adjustment setting to 0 Example of screen showing that three minutes and ten s...

Страница 39: ...sible 11 1 CB CB12 Min alternator voltage 12 0 12 1 CB CB12 Max alternator voltage 13 0 13 1 CB CB12 Min alternator frequency 14 0 14 1 CB CB12 Max alternator frequ ency 15 0 15 1 CB CB12 Option 3 mod...

Страница 40: ...gine overspeed impossible 53 1 module 5 QST30 engine general fault impossible 54 1 module 5 QST30 engine general alarm 55 0 impossible module 5 Engine oil high level 56 0 impossible module 4 Engine oi...

Отзывы: