4
10/01
Technicals characteristics _________________________________________________________________________________________________________________________________
55 - O
Oppttiioonn 33,, 44 aanndd 55 m
moodduulleess ((O
OPPTT3344))
Modular case, dimensions : 160x90x58
Programming specific to each module (dip-switch)
8 allocated inputs and 10 programmable outputs on option 3 for remote volt free contacts
8 programmable inputs and 10 programmable outputs on option 4 , with 24 preprogrammed options
Specific programming of some entries
66 - AAlltteerrnnaattoorr ccuurrrreenntt iinnppuutt
4-wire, unisolated, on current transformer with 5A secondary (not built into the electronics)
Measurements in true root mean square values
Measurement range: 60A to 5000A
77 - AAlltteerrnnaattoorr vvoollttaaggee iinnppuutt
4-wire (3ph + neutral), unisolated, with 12.5A-500Vac built in power bus in 50 and 60Hz
Measurements in true root mean square values
Frequency measurement on phase 1 for screen display and engine overspeed sensing
88 - M
Maaiinnss vvoollttaaggee m
maaiinnss 11
4-wire (3ph + neutral), unisolated, with 15A-600Vac built in power bus in 50 and 60Hz
No voltage and frequency measurements
99 - M
Maaiinnss vvoollttaaggee m
maaiinnss 22
2-wire (1ph + neutral), unisolated, with 10A-240Vac built in power bus in 50 and 60Hz
No voltage and frequency measurements
1100 - C
Chhaarrggee aalltteerrnnaattoorr iinnppuutt
Charge alternator excitation and fault
Starter hardware fail safe on software failure
1111 - C
Coom
mm
muunniiccaattiioonn
RS485 serial port with J-Bus protocol (Mod bus RTD)
9-pin SUB-D connector
Monitoring possible in local mode (
≤
1000meters)
Remote management possible with 2 modems (>1000m)
Optional monitoring/remote management software
1122 - C
CAAN
N LLiinnkk
Link between interface board and option module(s)
Standard CAN bus version 2.0b, 9-pin SUB-D connector for CC supply to module
1 connector on CB and CB1, 2 connectors on CB12
1133 - FFuussee pprrootteeccttiioonn
Fn, F1, F2, F3, 12.5A-500V fuses for alternator bus
Mains bus protected by circuit breaker in the ATS
F5, 10A fuse for the DC bus
F7, 2.5A delayed action fuse for the interface board
F6, 1A delayed action fuse for option 3 Module
F8, 1A delayed action fuse for option 4, 5 Module (CB12 only)
1144 - C
Coonnnneeccttiioonnss
Multi-pin (2 to 15 pins) connectors with polarizer
Number of connectors varies with interface board
Each connector has a specific use
1155 - PPrrooggrraam
mm
miinngg ooppttiioonnss
Multiple programming possibilities
Access code required to read/program