![SDMO MICS Telys Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/sdmo/mics-telys/mics-telys_instructions-for-use-manual_1220462011.webp)
10/01
3
__________________________________________________________________________________________________________________Technicals characteristics
11 - FFeeaattuurreess
Display module (DM)
Interface board available in 2 versions (CB, CB12) depending on customer optional equipment.
Option 3 module, option 4 module and option 5 module (OPT 334)
Block building system enabling multiple combinations.
Note: DM required in all combinations
22 - D
Diissppllaayy m
moodduullee (Fig. 2)
LCD screen, 8 lines 21 characters, built-in back-light and keyboard adjustable contrast
28 momentary push buttons (two types; 10 and 13 dia.)
15 display LEDs (alarms/warnings, faults/shutdowns, status, operating modes)
UL approved polycarbonate case supplied with cable and connector for connection to the interface board
Dimensions 192x144x70
Quick installation using brackets and nuts screws
IP65 on panel face with seal (not supplied), IP20 inside
Extremely user friendly man-machine interface: multiple-message screens, diagnostic, genset status, ...
33 - IInntteerrffaaccee bbooaarrdd ((FFiigg.. 11))
CB = Main board
CB12 = Main board with option 1 and option 2 built in
Electronics in a sheet steel case (base + lid)
Dimensions : 435x263x31
Voltage bus; alternator, mains and DC built into the printed circuit board (see paragraphs 7, 8, 9 and 13)
16 bit microcontroller, (Flash, RAM and EEPROM) memories, real-time clock, battery backup for time and date
Supply from 9 to 33Volts DC and from 6Volts DC, for voltage drop at start-up
All connections are built into the printed circuit board on both sides with full screen printing
44 - LLooggiiccaall//aannaalloogg II//O
O
All inputs and outputs are allocated to a specific use
(see tables below).
Note: Alarm or Fault selection via programming
Key:
A=Alarm, F=Fault, ana.=analog, C=Control
T=Transistor, R=Relay,
Ω
=resistive
Fig. 11 - C
CB12 bboard
Fig. 22 - D
Display m
module
* : France only
Type
Logical output description
CB
CB12
F
oil pressure
x
x
F
water temperature
x
x
A or F
day tank low fuel level
x
x
F
emergency stop
x
x
A or F
overload or short-circuit
x
x
C
water heater thermostat
x
x
C
external start-up command
x
x
F
radiator low water level
x
x
C
Mains
contactor home position
x
x
C
Stand-by
contactor home position
x
x
F
external emergency stop
x
x
F
oil temperature
x
F
low oil level
x
A or F
water heater failure
x
A or F
battery charger failure
x
A or F
differential or CIC trip
x
F
differential relay available
x
F
Constant Insulation Check available
x
F
air cooler disconnection
x
F
air cooler low water level
x
A or F
fuel pump 1 disconnection
x
A or F
retention
bund
x
C
bulk tank CF80
x
A or F
bulk tank low fuel level
x
C
EJP switch (*)
x
C
EJP start-up (*)
x
C
EJP advanced warning (*)
x
Type
Logical output description
CB
T
fuel solenoid control
x
T
starter 1 contr ol
x
T
engine
preglow control
x
T
water heater control
x
T
hooter control (general fault)
x
R
Mains
contactor control
x
R
Stand-by
contactor control
x
T
air damper control
T
starter 2 control
R
electro-flaps control
T
fuel pump 1 control
R
CIC remote contact
Type
Analogue input description
CB
Ω
oil pressure indication
x
Ω
water temperature indication
x