FV-40 Series Flame Detector
087-0056 REV F
48
A Specifications
Failure to review and understand the specifications for your model
could result in serious injury or death.
➣
In this appendix…
Technical Specifications
Electrical Specifications
Outputs
Mechanical Specifications
Environmental Specifications
A.1 Technical
Specifications
Please refer to the appropriate section depending on your detector model:
Triple IR F4-I3 / Multi IR F4-MM
Spectral Response
Three IR Bands
Detection Range
(at highest Sensitivity
Setting for 1ft
2
(0.1m
2
) pan
fire)
Fuel
ft. / m
Fuel
ft. / m
n-Heptane
215 / 65
Kerosene
150 / 45
Gasoline
215 / 65
Ethanol 95%
135 / 40
Diesel Fuel
150 / 45
Methanol
115 / 35
JP5
150 / 45
IPA (Isopropyl
Alcohol)
135 / 40
Methane*
100 / 30
Polypropylene
Pellets
16 / 5
LPG*
100 / 30
Office Paper
33 / 10
* 20" (0.5m) high, 8" (0.2m) width plume fire
Response Time
Typically 5 seconds
.
Adjustable Time Delay
Up to 30 seconds
Sensitivity Ranges
4 Sensitive ranges for 1 ft
2
(0.1m
2
) n-heptane pan fire from
50 ft. (15m) to 215 ft. (65m)