Installing the Detector
FV-40 Series Flame Detector
087-0056 REV F
28
2.2.1
Checking the Product Type
Check that your product has the configuration / options that you ordered.
Check the detailed part number on the label and compare this information
with the descriptions contained in
Model and Types
.
2.3 Required
Tools
The detector can be installed using general-purpose common tools
and equipment.
Table 16 lists the specific tools required to install the detector.
Table 16: Tools
Tool
Function
Hex Key ¼ inch
Mount the detector on the tilt mount
Hex Key
3
/
16
inch
Open and close detector cover (for wiring)
Flat Screw Driver 4 mm
Connect ground terminal
Flat Screw Driver 2.5 mm
Connect wires to the terminal blocks
For wiring, use color-coded conductors or suitable wire markings or labels.
12 to 20 AWG (0.5 mm² to 3.5 mm²) wires may be used for site wiring. The
selection of wire gauge should be based on the number of detectors used on
the same line and the distance from the control unit, in compliance with
specifications (see
General Instructions for Electrical Wiring
).