13
7. Push the “Arrows up-down” to page 3 of 5,
select
PROBE S1
and push
8. Push the “Arrows up-down” till select
“ratiom. 0/45barg”
then push
again
9. With “Arrow down” go to the next steps and
check all connections as shown on display
10. Push the “Arrow down” to move to Driver B
to page 4 of 5
11. Select
REFRIGERANT
and push the Enter
Button
then the “Arrows up-down” till the
Refrigerant
R744
.
12. Push again
to confirm
13. Always at page 4 of 5, check that
VALVE
is
Carel ExV
15. Push the “Arrows up-down” to page 5 of 5,
select
PROBE S3
and push
16.
Push the “Arrows up-down” till select
“ratiom. 0/45barg”
then push
again