![Scotsman MF 59 SPLIT Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/scotsman/mf-59-split/mf-59-split_service-manual_1218980014.webp)
12
25. With “Arrows up-down” go to page 5 of 9,
select
LowSH protect. threshold
and push
26. With “Arrows up-down” select
3K
and
27. With “Arrows up-down” move to
LowSH
protect. integral time
and push
28. With “Arrows up-down” select
10.0 s
and
push
29. With “Arrows up-down” go to page 6 of 9,
select
LOP protection threshold
and push
With “Arrows up-down” move to
-38°C
and
push
30.
With “Arrows up-down” move to
LOP
protection integral time
and push
31. With “Arrows up-down” move to
5s
and push
32. Push “Esc” to leave the REGULATION
MF 69 TWIN DRIVER CONFIGURATION-SETTING
PROCEDURE
1. Replace the Driver cover with the EVD
Display and provide power to the machine.
2. Display will show the page 1 of 5 with Driver
A as below
3. Push the “Arrow down” to page 2 of 5
4. Select
REFRIGERANT
and push the Enter
Button
then the “Arrows up-down” till the
Refrigerant
R744
.
5. Push again
to confirm
6. Always at page 2 of 5, check that
VALVE
is
Carel ExV