- 12 -
Parameter List for Elreha TARN1179 K004
No. Description
Code
Default
Setting
Range
P01 Actual sensor temperature in
°
C
(display only)
-
-
-40
°
C …110
°
C
P02 Control set point can be changed
at any time within the limits set by
P04 and P05
-
-2.0
°
C
P04…P05
P03 Switching differential (hysteresis)
of control set point
21
0.2K
0.2K…10K
P04 Highest adjustable set point
21
5.0
°
C
-35
°
C…100
°
C
P05 Lowest adjustable set point
21
-10
°
C
-35
°
C…P04
P06 Sensor Correction
21
0.0K
-10.0K…10.0K
P07 Minimum idle time of refrigeration
21
3 min
0…99 min
P08 Minimum run time of refrigeration
21
3 min
0…99 min
P09 Access code
-
0