Additional Maintenance: Bin Controls, Condenser
The bin controls use a system of infrared emitting
and receiving components to sense the build up of
ice in the bin. They are located at the bottom of the
ice outlet port. They must be free of mineral build
up to function properly. To check:
1. Remove front panel.
2. Push and release the off button.
3. Remove top and right side panels.
4. Remove the evaporator cover.
5. Remove the cube deflector.
6. Push into the freezing compartment the electric
eye brackets.
7. Examine the bottom of the brackets, there are
two sensors in each bracket, check that they are
clear of mineral build up. They may be wiped clean
with ice machine cleaner to assist in removal of the
build up.
Note: Do NOT use abrasive materials or cleaner
on the bin sensor lenses.
To Clean the Remote Air Cooled
Condenser
1. Disconnect and lock out the electrical power.
2. At the remote condenser, check for loose debris
on the roof, remove any near the condenser.
3. Check the fan blade and condenser for grease
or dust build up. Brush the surface (bottom) of the
condenser with a nylon brush to remove surface
dirt. Use a fin comb to straighten any bent fins.
Note: Air flow is UP, towards the fan.
If grease is present, use coil cleaner on the
condenser. Be sure to wipe up any excess coil
cleaner.
4. Reconnect the electrical power.
CME506R, 656R, 806R: AutoIQ Cubers
January 2000
Page 26
Bin Control Sensor,
Electric Eye Area
Bin
Controls in
Reservoir