7.10
SEL-700G Relay
Instruction Manual
Date Code 20170814
Communications
Communications Protocols
Figure 7.15
SEL Cable C387—SEL-700G to SEL-3010
Communications Protocols
Protocols
Although the SEL-700G supports a wide range of protocols, not all protocols
are available on all ports. In addition, not all hardware options support all protocols.
Be sure to select the correct hardware to support a particular protocol. For
example, if Modbus TCP is necessary for your application, be sure to order
the Ethernet option for
Port 1
. Table 7.3 shows the ports and the protocols
available on each port.
SEL Communications Protocols
SEL ASCII.
This protocol is described in SEL ASCII Protocol and
SEL Compressed ASCII.
This protocol provides compressed versions of
some of the ASCII commands. The compressed commands are
described in SEL ASCII Protocol and Commands, and the protocol is
described in Appendix C: SEL Communications Processors.
SEL-700G Relay
DTE*
9-Pin Male
D Subconnector
DCE**
9-Pin Male
D Subconnector
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
DCD***
RXD
TXD
GND
RTS
CTS
GND
+5 Vdc (IN)
RXD (OUT)
TXD (IN)
Not Used
GND
Not Used
RTS (IN)
CTS (OUT)
GND
Pin
Func.
Pin
Func.
Pin #
Pin #
SEL-3010 Event Messenger
*DTE = Data Terminal Equipment
**DCE = Data Communications Equipment (Modem, etc.)
***DC Voltage (+5 V) not available on front-panel EIA-232 port
Table 7.3
Protocols Supported on the Various Ports
PORT
Supported Protocol
PORT F
SEL ASCII and Compressed ASCII Protocols, SEL
BOOT
, File Transfer
Protocol, Modbus RTU Slave, C37.118 Protocol (synchrophasor data), and
Event Messenger
PORT 1
a
a
PORT 1 concurrently supports two Modbus, three DNP3 LAN/WAN, two FTP, two Telnet, two
C37.118 Protocol, one SNTP, and six IEC 61850 sessions.
Modbus TCP/IP, FTP, TCP/IP, IEC 61850, SNTP, DNP3 LAN/WAN, and
Telnet TCP/IP (SEL ASCII, Compressed ASCII), SEL Fast Meter, SEL Fast
Operate, SEL Fast SER, C37.118 Protocol (synchrophasor data)
PORT 2
All the protocols supported by
Port 3
PORT 3
SEL ASCII and Compressed ASCII Protocols, SEL Fast Meter, SEL Fast
Operate, SEL Fast SER, SEL Settings File Transfer, SEL M
IRRORED
B
ITS
,
DNP3, Modbus RTU Slave, C37.118 Protocol (synchrophasor data), and Event
Messenger
PORT 4
All the protocols supported by
Port 3
or DeviceNet
NOTE:
FTP, Modbus, and DeviceNet
protocols ignore the hide rules of the
settings.
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...