SEL-387-0, -5, -6 Relay Settings Sheet Group Settings (SET Command)
Thermal Element (SEL-387-6 Relay Only)
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20050919
Date _______________
Group______________
General Cooling System Constants
Nominal Insulation Life (1000–999999 hr)
ILIFE
=
Enable Default Constants (Y/N)
EDFTC
=
Transformer 1
Hot-Spot Thermal Time Constant (0.01–2.00 hr)
Ths1
=
Constant to Calc. FAA (0–100000)
BFFA1
=
Cooling Stage 1 Constants
Top-Oil Rise/Amb (0.1–100.0ºC)
THor11
=
Hot-Spot Cond. Rise/Top Oil (0.1–100.0ºC)
THgr11
=
Ratio Losses (0.0–100.0)
RATL11
=
Oil Thermal Time Constant (0.1–20.0 hr)
OTR11
=
Oil Exponent (0.1–5)
EXPn11
=
Winding Exponent (0.1–5)
EXPm11
=
Cooling Stage 2 Constants
Top-Oil Rise/Amb (0.1–100.0ºC)
THor12
=
Hot-Spot Cond. Rise/Top Oil (0.1–100.0ºC)
THgr12
=
Ratio Losses (0.0–100.0)
RATL12
=
Oil Thermal Time Constant (0.1–20.0 hr)
OTR12
=
Oil Exponent (0.1–5)
EXPn12
=
Winding Exponent (0.1–5)
EXPm12
=
Cooling Stage 3 Constants
Top-Oil Rise/Amb (0.1–100.0ºC)
THor13
=
Hot-Spot Cond. Rise/Top Oil (0.1–100.0ºC)
THgr13
=
Ratio Losses (0.0–100.0)
RATL13
=
Oil Thermal Time Constant (0.1–20.0 hr)
OTR13
=
Oil Exponent (0.1–5)
EXPn13
=
Winding Exponent (0.1–5)
EXPm13
=
Transformer 2
Hot-Spot Thermal Time Constant (0.01–2.00 hr)
Ths2
=
Constant to Calc. FAA (0–100000)
BFFA2
=
Cooling Stage 1 Constants
Top-Oil Rise/Amb (0.1–100.0ºC)
THor21
=
Hot-Spot Cond. Rise/Top Oil (0.1–100.0ºC)
THgr21
=
Ratio Losses (0.0–100.0)
RATL21
=
Содержание SEL-387-0
Страница 10: ...This page intentionally left blank ...
Страница 16: ...This page intentionally left blank ...
Страница 56: ...This page intentionally left blank ...
Страница 350: ...This page intentionally left blank ...
Страница 388: ...This page intentionally left blank ...
Страница 456: ...This page intentionally left blank ...
Страница 494: ...This page intentionally left blank ...
Страница 528: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...