4.14
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20050919
Control Logic
Output Contacts
Output Contacts
SEL
OGIC
control equation settings OUT101 through OUT107 and OUT201
through OUT212 control Relay Word bits having the same names. These
Relay Word bits in turn control the output contacts
OUT101
through
OUT107
and
OUT201
through
OUT212
(interface board). Alarm logic/circuitry controls the
ALARM
output contact.
Factory Settings
Example
In the factory SEL
OGIC
control equation settings, all seven standard main
board output contacts are used:
OUT101 =
TRIP1
Used to trip Breaker 1
OUT102 =
TRIP2
Used to trip Breaker 2
OUT103 =
TRIP3
Used to trip Breaker 3
OUT104 =
TRIP4
Used to energize 86 device for tripping Breakers 1
through 3
OUT105 =
CLS1
Used to close Breaker 1
OUT106 =
CLS2
Used to close Breaker 2
OUT107 =
CLS3
Used to close Breaker 3
Operation of Output
Contacts for Different
Output Contact Types
Output Contacts OUT101 through OUT107 and OUT201 through OUT212
The execution of the serial port command
PULSE
xxx
(
xxx
=
OUT101
–
OUT107
,
OUT201
–
OUT212
), asserts the corresponding Relay Word bit (e.g., OUT104) to
logical 1, for one or more seconds as defined by the user. The assertion of
SEL
OGIC
control equation setting OUT
m
(
m
= 101–107, 201–212) to logical 1
also asserts the corresponding Relay Word bit OUT
m
to logical 1.
The assertion of Relay Word bit OUT
m
to logical 1 causes the energization of
the corresponding output contact OUT
m
coil. Depending on the contact type
(a or b), the output contact closes or opens. An a type output contact is open
when the output contact coil is de-energized and closed when the output
contact coil is energized. A b type output contact is closed when the output
contact coil is de-energized and open when the output contact coil is
energized. Solder jumpers JMP22 through JMP29 (main board) and JMP17
through JMP28 (interface board) permit the user to configure any
OUTm
contact to either an a or b type.
OUT101
through
OUT107
are factory-configured
as type a, as are
OUT201
through
OUT212
if the additional interface board is
ordered.
The state of
OUTm
remains the same while a setting change is in progress.
However, once the new settings are enabled, the SEL
OGIC
control equation
setting for
OUTm
will determine the new state of
OUTm
.
OUT107
coil operation may be set to follow that of the
ALARM
contact by setting
jumper JMP23 in the left position on the main board.
OUT107
then will not
respond to Relay Word bit OUT107. The
OUT107
contact configuration can be
set as a or b, as noted above. See
for more information.
Содержание SEL-387-0
Страница 10: ...This page intentionally left blank ...
Страница 16: ...This page intentionally left blank ...
Страница 56: ...This page intentionally left blank ...
Страница 350: ...This page intentionally left blank ...
Страница 388: ...This page intentionally left blank ...
Страница 456: ...This page intentionally left blank ...
Страница 494: ...This page intentionally left blank ...
Страница 528: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...