2-14
Installation
Date Code 20001006
SEL-351 Instruction Manual
Models 0351xT and 0351xY part numbers with a numeral “3” in the field underlined below
(sample part numbers) indicate delta-connected voltage inputs:
0351xT435331411
0351xYH43542X1
Models 0351x0 and 0351x1
Note the signal labels (VA, VB, VC, N, VS, NS) on terminals Z09 through Z14. Figure 1.3 shows
the internal connection (wye or delta) for terminals VA, VB, VC, and N. Note also that VS/NS is
a separate single-phase voltage input.
Wye-Connected Voltages
Any of the single-phase voltage inputs (i.e., VA-N, VB-N, VC-N, or VS-NS) can be connected to
voltages up to 150 V (or 300 V; see Table 1.2) continuous. Figure 2.7 and Figure 2.9 through
Figure 2.12 show examples of wye-connected voltages. Frequency is determined from the voltages
connected to terminals VA-N and VS-NS (see subsections
Synchronism Check Elements
and
Frequency Elements
in
Section 3: Overcurrent, Voltage, Synchronism Check, Frequency, and
Power Elements
). Model 0351x0 or 0351x1 part numbers with a numeral “2” or “5” in the field
underlined below (model 0351x0 sample part number shown) indicate wye-connected voltage
inputs:
0351x0H42542X1
0351x0H45542X1
Delta-Connected Voltages
Phase-to-phase voltage (up to 300 V continuous) can be connected to voltage inputs VA-VB, VB-
VC, or VC-VA. Figure 2.8 shows an example of open-delta connected potential transformers
connected to voltage inputs VA, VB, and VC. No connections are made to terminal N. Frequency
is determined from the voltages connected to terminals VA-VB and VS-NS (see subsections
Synchronism Check Elements
and
Frequency Elements
in
Section 3: Overcurrent, Voltage,
Synchronism Check, Frequency, and Power Elements
).
Model 0351x0 or 0351x1 part numbers with a numeral “3” in the field underlined below (model
0351x0 sample part number shown) indicate delta-connected voltage inputs:
0351x0H43542X1
Serial Ports
Refer to Table 10.1 for information on the serial ports available on the different SEL-351 Relay
models. All ports are independent - you can communicate to any combination simultaneously.
Serial Port 1 on all the SEL-351 Relay models is an EIA-485 port (4-wire). The Serial Port 1
plug-in connector accepts wire size AWG 24 to 12. Strip the wires 0.31 inches (8 mm) and install
with a small slotted-tip screwdriver. For models 0351x0, 0351x1, and 0351xY, the Serial Port 1
connector has extra positions for IRIG-B time-code signal input (see Table 10.3; see following
discussion on IRIG-B time code input).
Содержание SEL-351
Страница 14: ...Courtesy of NationalSwitchgear com ...
Страница 16: ...Courtesy of NationalSwitchgear com ...
Страница 40: ...Courtesy of NationalSwitchgear com ...
Страница 74: ...Courtesy of NationalSwitchgear com ...
Страница 146: ...Courtesy of NationalSwitchgear com ...
Страница 186: ...Courtesy of NationalSwitchgear com ...
Страница 220: ...Courtesy of NationalSwitchgear com ...
Страница 304: ...Courtesy of NationalSwitchgear com ...
Страница 340: ...Courtesy of NationalSwitchgear com ...
Страница 380: ...Courtesy of NationalSwitchgear com ...
Страница 450: ...Courtesy of NationalSwitchgear com ...
Страница 506: ...Courtesy of NationalSwitchgear com ...
Страница 528: ...Courtesy of NationalSwitchgear com ...
Страница 534: ...Courtesy of NationalSwitchgear com ...
Страница 536: ...Courtesy of NationalSwitchgear com ...
Страница 550: ...Courtesy of NationalSwitchgear com ...
Страница 562: ...Courtesy of NationalSwitchgear com ...
Страница 570: ...Courtesy of NationalSwitchgear com ...
Страница 584: ...Courtesy of NationalSwitchgear com ...
Страница 602: ...Courtesy of NationalSwitchgear com ...
Страница 610: ...Courtesy of NationalSwitchgear com ...