12-2
Standard Event Reports, Sag/Swell/Interruption Report, and SER
Date Code 20001006
SEL-351 Instruction Manual
Set the event report length with the LER setting. Set the prefault length with the PRE setting. See
the SET G command in Table 9.1 and corresponding Settings Sheet 17 of 22 in
Section 9: Setting
the Relay
for instructions on setting the LER and PRE settings.
Changing the LER setting will erase all events stored in nonvolatile memory. Changing the PRE
setting has no effect on the nonvolatile reports.
Standard Event Report Triggering
The relay triggers (generates) a standard event report when any of the following occur:
•
Relay Word bit TRIP asserts
•
Programmable SEL
OGIC
®
Control Equation setting ER asserts to logical 1
•
TRI (Trigger Event Reports) serial port command executed
•
Output contacts OUT1 through OUT11 (Model 0351xT) or OUT101 through OUT107
(Models 0351x0, 0351x1, and 0351xY) pulsed via the serial port or front-panel PUL (Pulse
Output Contact) command
Relay Word Bit TRIP
Refer to Figure 5.1. If Relay Word bit TRIP asserts to logical 1, an event report is automatically
generated. Thus, any condition that causes a trip does not have to be entered in SEL
OGIC
Control
Equation setting ER.
For example, SEL
OGIC
Control Equation trip setting TR is unsupervised. Any trip condition that
asserts in setting TR causes the TRIP Relay Word bit to assert immediately. The factory setting
for trip setting TR is:
TR = OC + 51PT + 51GT + 81D1T + LB3 + 50P1 * SH0
If any of the individual conditions OC, 51PT, 51GT, 81D1T, LB3, or 50P1 * SH0 assert, Relay
Word bit TRIP asserts, and an event report is automatically generated. Thus, these conditions do
not have to be entered in SEL
OGIC
Control Equation setting ER.
Relay Word bit TRIP (in Figure 5.1) is usually assigned to an output contact for tripping a circuit
breaker (e.g., SEL
OGIC
Control Equation setting OUT1 = TRIP).
Programmable SEL
OGIC
Control Equation Setting ER
The programmable SEL
OGIC
Control Equation event report trigger setting ER is set to trigger
standard event reports for conditions other than trip conditions. When setting ER sees a logical 0
to logical 1 transition, it generates an event report (if the SEL-351 Relay is not already generating
a report that encompasses the new transition). The factory setting is:
ER = /51P + /51G + /OUT3
Содержание SEL-351
Страница 14: ...Courtesy of NationalSwitchgear com ...
Страница 16: ...Courtesy of NationalSwitchgear com ...
Страница 40: ...Courtesy of NationalSwitchgear com ...
Страница 74: ...Courtesy of NationalSwitchgear com ...
Страница 146: ...Courtesy of NationalSwitchgear com ...
Страница 186: ...Courtesy of NationalSwitchgear com ...
Страница 220: ...Courtesy of NationalSwitchgear com ...
Страница 304: ...Courtesy of NationalSwitchgear com ...
Страница 340: ...Courtesy of NationalSwitchgear com ...
Страница 380: ...Courtesy of NationalSwitchgear com ...
Страница 450: ...Courtesy of NationalSwitchgear com ...
Страница 506: ...Courtesy of NationalSwitchgear com ...
Страница 528: ...Courtesy of NationalSwitchgear com ...
Страница 534: ...Courtesy of NationalSwitchgear com ...
Страница 536: ...Courtesy of NationalSwitchgear com ...
Страница 550: ...Courtesy of NationalSwitchgear com ...
Страница 562: ...Courtesy of NationalSwitchgear com ...
Страница 570: ...Courtesy of NationalSwitchgear com ...
Страница 584: ...Courtesy of NationalSwitchgear com ...
Страница 602: ...Courtesy of NationalSwitchgear com ...
Страница 610: ...Courtesy of NationalSwitchgear com ...