Protocol Settings (See Below)
Protocol (SEL, LMD, DNP, MBA, MBB, MB8A, MB8B)
PROTO =
Protocol Settings
Set PROTO = SEL for standard SEL ASCII protocol. For SEL Distributed
Port Switch Protocol (LMD), set PROTO = LMD. Refer to
Appendix C
for details on the LMD
protocol. For Distributed Network Protocol (DNP), set PROTO = DNP. Refer to
Appendix H
for details on DNP protocol. For M
IRRORED
B
ITS
, set PROTO = MBA, MBB, MB8A, or MB8B.
Refer to
Appendix I
for details on M
IRRORED
B
ITS
.
The following settings are used if PROTO = LMD.
LMD Prefix (@, #, $, %, &)
PREFIX =
LMD Address (01 - 99)
ADDR =
LMD Settling Time (0 - 30 seconds)
SETTLE =
Communications Settings
Baud Rate (300, 1200, 2400, 4800, 9600, 19200, 38400)
SPEED =
Data Bits (6, 7, 8)
BITS =
Parity (O, E, N) {Odd, Even, None}
PARITY =
Stop Bits (1, 2)
STOP =
Other Port Settings (See Below)
Time-out (0 - 30 minutes)
T_OUT =
Send Auto Messages to Port (Y, N, DTA)
AUTO =
Enable Hardware Handshaking (Y, N, MBT)
RTSCTS =
Fast Operate Enable (Y, N)
FASTOP =
Other Port Settings
Set T_OUT to the number of minutes of serial port inactivity for an
automatic log out. Set T_OUT = 0 for no port time out.
Set AUTO = Y to allow automatic messages at the serial port. Set AUTO = DTA to use the serial
port with an SEL-DTA2 Display/Transducer Adapter.
Set RTSCTS = Y to enable hardware handshaking. With RTSCTS = Y, the relay will not send
characters until the CTS input is asserted. Also, if the relay is unable to receive characters, it
deasserts the RTS line. Setting RTSCTS is not applicable to serial Port 1 (EIA-485) or a port
configured for SEL Distributed Port Switch Protocol.
Set RTSCTS = MBT is only available at 9600 baud (SPEED selection). In this mode, the relay
deaaserts the RTS line and does not monitor the CTS line. This selection is sometimes used with
PROTO = MBA or MBB. See
Appendix I
.
Set FASTOP = Y to enable binary
Fast Operate
messages at the serial port. Set FASTOP = N to
block binary
Fast Operate
messages. Refer to
Appendix D
for the description of the SEL-351
Relay
Fast Operate
commands.
Содержание SEL-351
Страница 14: ...Courtesy of NationalSwitchgear com ...
Страница 16: ...Courtesy of NationalSwitchgear com ...
Страница 40: ...Courtesy of NationalSwitchgear com ...
Страница 74: ...Courtesy of NationalSwitchgear com ...
Страница 146: ...Courtesy of NationalSwitchgear com ...
Страница 186: ...Courtesy of NationalSwitchgear com ...
Страница 220: ...Courtesy of NationalSwitchgear com ...
Страница 304: ...Courtesy of NationalSwitchgear com ...
Страница 340: ...Courtesy of NationalSwitchgear com ...
Страница 380: ...Courtesy of NationalSwitchgear com ...
Страница 450: ...Courtesy of NationalSwitchgear com ...
Страница 506: ...Courtesy of NationalSwitchgear com ...
Страница 528: ...Courtesy of NationalSwitchgear com ...
Страница 534: ...Courtesy of NationalSwitchgear com ...
Страница 536: ...Courtesy of NationalSwitchgear com ...
Страница 550: ...Courtesy of NationalSwitchgear com ...
Страница 562: ...Courtesy of NationalSwitchgear com ...
Страница 570: ...Courtesy of NationalSwitchgear com ...
Страница 584: ...Courtesy of NationalSwitchgear com ...
Страница 602: ...Courtesy of NationalSwitchgear com ...
Страница 610: ...Courtesy of NationalSwitchgear com ...